资源描述

《BS-EN-60700-1-1999 IEC-60700-1-1998.pdf》由会员分享,可在线阅读,更多相关《BS-EN-60700-1-1999 IEC-60700-1-1998.pdf(44页珍藏版)》请在三一文库上搜索。

1、BRITISH STANDARD BS EN 60700-1:1999 IEC 60700-1:1998 Incorporating Amendment No. 1 Thyristor valves for high voltage direct current (HVDC) power transmission Part 1: Electrical testing The European Standard EN 60700-1:1998, with the incorporation of amendment A1:2003, has the status of a British Sta

2、ndard ICS 31.080.20 ? Licensed Copy: sheffieldun sheffieldun, na, Fri Nov 10 17:06:09 GMT+00:00 2006, Uncontrolled Copy, (c) BSI BS EN 60700-1:1999 This British Standard, having been prepared under the direction of the Electrotechnical Sector Committee, was published under the authority of the Stand

3、ards Committee and comes into effect on 15 February 1999 BSI 12 September 2003 ISBN 0 580 30872 3 National foreword This British Standard is the official English language version of EN 60700-1:1998, including amendment A1:2003. It is identical with IEC 60700-1:1998, including amendment 1:2003. The s

4、tart and finish of text introduced or altered by amendment is indicated in the text by tags !“. Tags indicating changes to CENELEC text carry the number of the CENELEC amendment. For example text altered by CENELEC amendment A1 is indicated by !“. The UK participation in its preparation was entruste

5、d to Technical Committee PEL/22, Static power convertors, which has the responsibility to: aid enquirers to understand the text; present to the responsible international/European committee any enquiries on the interpretation, or proposals for change, and keep the UK interests informed; monitor relat

6、ed international and European developments and promulgate them in the UK. A list of organizations represented on this committee can be obtained on request to its secretary. Cross-references The British Standards which implement international or European publications referred to in this document may

7、be found in the BSI Catalogue under the section entitled “International Standards Correspondence Index”, or by using the “Search” facility of the BSI Electronic Catalogue or of British Standards Online. This publication does not purport to include all the necessary provisions of a contract. Users ar

8、e responsible for its correct application. Compliance with a British Standard does not of itself confer immunity from legal obligations. Summary of pages This document comprises a front cover, an inside front cover, pages i and ii, the EN title page, pages 2 to 40, an inside back cover and a back co

9、ver. The BSI copyright notice displayed in this document indicates when the document was last issued. Amendments issued since publication Amd. No.DateComments 1448012 September 2003See national foreword Licensed Copy: sheffieldun sheffieldun, na, Fri Nov 10 17:06:09 GMT+00:00 2006, Uncontrolled Copy

10、, (c) BSI EUROPEAN STANDARD NORME EUROPENNE EUROPISCHE NORM EN 60700-1 October 1998 + A1 April 2003 ICS 29.200 Descriptors: Electric power transmission, direct current, high voltage equipment, switchgear semiconductor valves, thyristors, electrical tests English version Thyristor valves for high vol

11、tage direct current (HVDC) power transmission Part 1: Electrical testing (includes amendment A1:2003) (IEC 60700-1:1998 + A1:2003) Valves thyristors pour le transport dnergie en courant continu haute tension (CCHT) Partie 1: Essais lectriques (inclut lamendement A1:2003) (CEI 60700-1:1998 + A1:2003)

12、 Thyristorventile fr Hochspannungs- gleichstrom-Energiebertragung Teil 1: Elektrische Prfung (enthlt nderung A1:2003) (IEC 60700-1:1998 + A1:2003) This European Standard was approved by CENELEC on 1998-10-01. Amendment A1 was approved by CENELEC on 2003-04-01. CENELEC members are bound to comply wit

13、h the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the Central Secretari

14、at or to any CENELEC member. This European Standard exists in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CENELEC member into its own language and notified to the Central Secretariat has the same status as the o

15、fficial versions. CENELEC members are the national electrotechnical committees of Austria, Belgium, Czech Republic, Denmark, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Luxembourg, Malta, Netherlands, Norway, Portugal, Slovakia, Spain, Sweden, Switzerland and United Kingdom.

16、CENELEC European Committee for Electrotechnical Standardization Comit Europen de Normalisation Electrotechnique Europisches Komitee fr Elektrotechnische Normung Central Secretariat: rue de Stassart 35, B-1050 Brussels 1998 CENELEC All rights of exploitation in any form and by any means reserved worl

17、dwide for CENELEC members. Ref. No. EN 60700-1:1998 + A1:2003 E Licensed Copy: sheffieldun sheffieldun, na, Fri Nov 10 17:06:09 GMT+00:00 2006, Uncontrolled Copy, (c) BSI EN 60700-1:1998 BSI 12 September 20032 Foreword The text of document 22F/44/FDIS, future edition 1 of IEC 60700-1, prepared by SC

18、 22F, Power electronics for electrical transmission and distribution systems, of IEC TC 22, Power electronics, was submitted to the IEC-CENELEC parallel vote and was approved by CENELEC as EN 60700-1 on 1998-10-01. The following dates were fixed: Annexes designated “normative” are part of the body o

19、f the standard. Annexes designated “informative” are given for information only. In this standard, Annex A, Annex B and Annex ZA are normative and Annex C is informative. Annex ZA has been added by CENELEC. Endorsement notice The text of the International Standard IEC 60700-1:1998 was approved by CE

20、NELEC as a European Standard without any modification. Foreword to amendment A1 The text of document 22F/81/FDIS, future amendment 1 to IEC 60700-1:1998, prepared by SC 22F, Power electronics for electrical transmission and distribution systems, of IEC TC 22, Power electronic systems and equipment,

21、was submitted to the IEC-CENELEC parallel vote and was approved by CENELEC as amendment A1 to EN 60700-1:1998 on 2003-04-01. The following dates were fixed: Annexes designated “normative” are part of the body of the standard. In this standard Annex ZA is normative. Annex ZA has been added by CENELEC

22、. Endorsement notice The text of amendment 1:2003 to the International Standard IEC 60700-1:1998 was approved by CENELEC as an amendment to the European Standard without any modification. latest date by which the EN has to be implemented at national level by publication of an identical national stan

23、dard or by endorsement(dop) 1999-07-01 latest date by which the national standards conflicting with the EN have to be withdrawn(dow) 2001-07-01 latest date by which the amendment has to be implemented at national level by publication of an identical national standard or by endorsement(dop) 2004-01-0

24、1 latest date by which the national standards conflicting with the amendment have to be withdrawn(dow) 2006-04-01 Licensed Copy: sheffieldun sheffieldun, na, Fri Nov 10 17:06:09 GMT+00:00 2006, Uncontrolled Copy, (c) BSI EN 60700-1:1998 BSI 12 September 2003 3 Contents Page Foreword2 1Scope5 2Normat

25、ive references5 3Definitions5 4General requirements7 4.1Guidelines for the performance of type tests7 4.1.1Evidence in lieu7 4.1.2Test object8 4.1.3Sequence of tests8 4.1.4Test procedures8 4.1.5Ambient temperature for testing8 4.1.6Frequency for testing8 4.1.7Test reports8 4.2Atmospheric correction8

26、 4.3Treatment of redundancy8 4.3.1Dielectric tests8 4.3.2Operational tests9 4.4Criteria for successful type testing9 4.4.1Criteria applicable to thyristor levels9 4.4.2Criteria applicable to the valve as a whole10 5List of type tests11 6Dielectric tests on valve support11 6.1Purpose of tests11 6.2Te

27、st object12 6.3Test requirements12 6.3.1Valve support d.c. voltage test12 6.3.2Valve support a.c. voltage test12 6.3.3Valve support switching impulse test13 6.3.4Valve support lightning impulse test13 7Dielectric tests for multiple valve units (MVU)13 7.1Purpose of tests13 7.2Test object13 7.3Test r

28、equirements14 7.3.1MVU d.c. voltage test to earth14 7.3.2MVU a.c. voltage test14 7.3.3MVU switching impulse test15 7.3.4MVU lightning impulse test15 Page 8Dielectric tests between valve terminals16 8.1Purpose of tests16 8.2Test object16 8.3Test requirements17 8.3.1Valve d.c. voltage test17 8.3.2Valv

29、e a.c. voltage test17 8.3.3Valve impulse tests (general)19 8.3.4Valve switching impulse test19 8.3.5Valve lightning impulse test20 8.3.6Valve steep front impulse test20 8.4Valve non-periodic firing test20 8.4.1Purpose of test20 8.4.2Test object21 8.4.3Test requirements21 9Periodic firing and extinct

30、ion tests22 9.1Purpose of tests22 9.2Test object22 9.3Test requirements22 9.3.1Maximum continuous operating duty tests23 9.3.2Maximum temporary operating duty test ( = 90)24 9.3.3Minimum a.c. voltage tests25 9.3.4Temporary undervoltage test26 9.3.5Intermittent direct current tests27 10Tests with tra

31、nsient forward voltage during the recovery period27 10.1Purpose of tests27 10.2Test object27 10.3Test requirements27 11Valve fault current tests28 11.1Purpose of tests28 11.2Test object:28 11.3Test requirements28 11.3.1One-loop fault current test with re-applied forward voltage29 11.3.2Multiple-loop

32、 fault current test without re-applied forward voltage30 12Tests for valve insensitivity to electromagnetic disturbance30 12.1Purpose of tests30 12.2Test object31 Licensed Copy: sheffieldun sheffieldun, na, Fri Nov 10 17:06:09 GMT+00:00 2006, Uncontrolled Copy, (c) BSI EN 60700-1:1998 BSI 12 Septemb

33、er 20034 Page 12.3 Test requirements31 12.3.1 Approach one31 12.3.2 Approach two31 12.3.3 Acceptance criteria31 13 Testing of special features31 13.1 Purpose of tests31 13.2 Test object31 13.3 Test requirements32 14 Production tests32 14.1 Purpose of tests32 14.2 Test object32 14.3 Test requirements

34、32 14.4 Production test objectives32 14.4.1 Visual inspection32 14.4.2 Connection check32 14.4.3 Voltage-grading circuit check32 14.4.4 Voltage withstand check32 14.4.5 Partial discharge tests32 14.4.6 Check of auxiliaries33 14.4.7 Firing check33 14.4.8 Pressure test33 15 Method for loss determinati

35、on33 16 Presentation of type test results33 Annex A (normative) Test safety factors34 Annex B (normative) Partial discharge measurements37 Annex C (informative) Fault tolerance capability39 Annex ZA (normative) Normative references to international publications with their corresponding European publ

36、ications40 Figure 1 Steep front impulse test voltage6 Table 1 Thyristor level faults permitted during type tests10 Table 2 List of type tests11 Licensed Copy: sheffieldun sheffieldun, na, Fri Nov 10 17:06:09 GMT+00:00 2006, Uncontrolled Copy, (c) BSI EN 60700-1:1998 BSI 12 September 2003 5 1 Scope T

37、his standard applies to thyristor valves with metal oxide surge arresters directly connected between the valve terminals, for use in a line commutated converter for high voltage d.c. power transmission or as part of a back-to-back link. It is restricted to electrical type and production tests. The t

38、ests specified in this standard are based on air insulated valves. For other types of valves, the test requirements and acceptance criteria must be agreed. 2 Normative references The following normative documents contain provisions which, through reference in this text, constitute provisions of this

39、 part of IEC 60700. At the time of publication, the editions indicated were valid. All normative documents are subject to revision, and parties to agreements based on this part of IEC 60700 are encouraged to investigate the possibility of applying the most recent editions of the normative documents

40、indicated below. Members of IEC and ISO maintain registers of currently valid International Standards. ISO/IEC Guide 25:1990, General requirements for the competence of calibration and testing laboratories. IEC 60060, High-voltage test techniques. IEC 60060-1:1989, High-voltage test techniques Part

41、1: General definitions and test requirements. IEC 60071-1:1993, Insulation co-ordination Part 1: Definitions, principles and rules. IEC 60099, Surge arresters. IEC 60270:1981, Partial discharge measurements. !IEC 61803:1999, Determination of power losses in high-voltage direct current (HVDC) convert

42、er stations.“ 3 Definitions For the purpose of this part of IEC 60700, the following definitions apply. 3.1 Insulation co-ordination terms 3.1.1 test withstand voltage value of a test voltage of standard waveshape at which a new valve, with unimpaired integrity, does not show any disruptive discharg

43、e and meets all other acceptance criteria specified for the particular test, when subjected to a specified number of applications or a specified duration of the test voltage, under specified conditions 3.1.2 steep front impulse fast-front voltage impulse whose time to peak is less than that of a sta

44、ndard lightning impulse but not less than that of a very-fast-front voltage as defined in IEC 60071-1. For this standard, a steep front impulse voltage for test purposes is defined by Figure 1 3.1.3 internal and external insulation air external to the components and insulating materials of the valve

45、, but contained within the profile of the valve or multiple valve unit is considered as part of the internal insulation system of the valve. The external insulation is the air between the external surface of the valve or multiple valve unit and its surroundings 3.1.4 valve protective firing means of

46、 protecting the thyristors from excessive voltage by firing them at a predetermined voltage Licensed Copy: sheffieldun sheffieldun, na, Fri Nov 10 17:06:09 GMT+00:00 2006, Uncontrolled Copy, (c) BSI EN 60700-1:1998 6 BSI 12 September 2003 3.2 Valve construction terms 3.2.1 valve support that part of

47、 the valve which mechanically supports and electrically insulates from earth the active part of the valve which houses the valve sections NOTEA part of a valve which is clearly identifiable in a discrete form to be a valve support may not exist in all designs of valves. 3.2.2 valve structure physica

48、l structure holding the thyristor levels of a valve which is insulated to the appropriate voltage above earth potential NOTES U = Specified peak value of steep front impulse test voltage (kV) S = Specified steepness of steep front impulse test voltage (kV/4s) T1 = Virtual front time = The following

49、conditions shall be satisfied: a) The peak value of the recorded test voltage shall be U 3 %. This tolerance is the same as that in IEC 60060 for standard lightning impulse. b) Over a voltage excursion of not less than 0,6 U, the rising portion of the recorded test voltage shall be entirely contained between two parallel lines of steepness S and separation 0,2 T1. c) The value of the test voltage at T2 shall not be lower than 0,5 U. T2 is defined as t