AS 3823-1-2(A3-2006) Performance of electrical appliances—Airconditioners and heat pumps Part 1-2 Test Methods—Ducted air conditioners and air-to-air heat pumps—Testing and rating of performance.pdf

上传人:韩长文 文档编号:3641833 上传时间:2019-09-19 格式:PDF 页数:4 大小:105KB
返回 下载 相关 举报
AS 3823-1-2(A3-2006) Performance of electrical appliances—Airconditioners and heat pumps Part 1-2 Test Methods—Ducted air conditioners and air-to-air heat pumps—Testing and rating of performance.pdf_第1页
第1页 / 共4页
AS 3823-1-2(A3-2006) Performance of electrical appliances—Airconditioners and heat pumps Part 1-2 Test Methods—Ducted air conditioners and air-to-air heat pumps—Testing and rating of performance.pdf_第2页
第2页 / 共4页
AS 3823-1-2(A3-2006) Performance of electrical appliances—Airconditioners and heat pumps Part 1-2 Test Methods—Ducted air conditioners and air-to-air heat pumps—Testing and rating of performance.pdf_第3页
第3页 / 共4页
AS 3823-1-2(A3-2006) Performance of electrical appliances—Airconditioners and heat pumps Part 1-2 Test Methods—Ducted air conditioners and air-to-air heat pumps—Testing and rating of performance.pdf_第4页
第4页 / 共4页
亲,该文档总共4页,全部预览完了,如果喜欢就下载吧!
资源描述

《AS 3823-1-2(A3-2006) Performance of electrical appliances—Airconditioners and heat pumps Part 1-2 Test Methods—Ducted air conditioners and air-to-air heat pumps—Testing and rating of performance.pdf》由会员分享,可在线阅读,更多相关《AS 3823-1-2(A3-2006) Performance of electrical appliances—Airconditioners and heat pumps Part 1-2 Test Methods—Ducted air conditioners and air-to-air heat pumps—Testing and rating of performance.pdf(4页珍藏版)》请在三一文库上搜索。

1、 ISBN 0 7337 7282 X AS/NZS 3823.1.2/Amdt 3/2006-02-25 STANDARDS AUSTRALIA/STANDARDS NEW ZEALAND Amendment No. 3 to AS/NZS 3823.1.2:2001 Performance of electrical appliancesAirconditioners and heat pumps Part 1.2: Test MethodsDucted air conditioners and air-to-air heat pumpsTesting and rating of perf

2、ormance REVISED TEXT The 2001 edition of AS/NZS 3823.1.2 is amended as follows; the amendments should be inserted in the appropriate places. SUMMARY: This Amendment applies to the Preface and Appendix ZZ. Published on 25 February 2006. Approved for publication in New Zealand on behalf of the Standar

3、ds Council of New Zealand on 21 December 2005. Preface Add the following reference after AS/NZS 3823.1.1 (as inserted by Amendment No. 1 2002) 62301 Household electrical appliancesMeasurement of standby power Clause 1.1 Delete Clause 1.1 as amended by Amendment No. 1 2002 and replace with the follow

4、ing: This Standard specifies the conditions on which the capacity and energy consumption of factory-made residential, commercial and industrial electrically driven, mechanical- compression, single-package and split-system non-ducted airconditioners employing air- cooled condensers and non-ducted air

5、-to-air heat pumps are based. The Standard also specifies the test methods to be applied for determining the capacity and efficiency ratings. This Standard covers equipment utilizing one or more refrigeration systems with one outdoor unit and one or more indoor units controlled by a single thermosta

6、t/controller. This Standard covers equipment utilizing single, multiple and variable capacity components. NOTE: Air conditioners with water cooled condensers have been excluded from this part and are now covered under the requirements of AS/NZS 3823.1.3. Clause 1.4 Add the following new Clause: This

7、 Standard does not cover the determination of seasonal efficiencies which may be required in some countries. Table 6 Delete the second test condition for test voltage and replace with the following: (b) 90% of the lower rated voltage and 110% of the higher rated voltage except that where the higher

8、rated voltage is 240 V, the maximum required test voltage shall be 253 V. AMDT No. 3 FEB 2006 AMDT No. 3 FEB 2006 AMDT No. 3 FEB 2006 AMDT No. 3 FEB 2006 Clause 6.2.1 Delete text and replace with the following: Where possible equipment shall be rated for capacity by the calorimeter method. Where thi

9、s is not possible, the indoor air-enthalpy test method may be used. Clause 6.6 and Clause 6.7 Add new Clauses 6.6 and 6.7 as follows: 6.6 Standby power and crank case heaters 6.6.1 General Measurements of standby power and crank case heater power shall be undertaken in accordance with the procedures

10、 and instruments specified in AS/NZS 62301 and shall be determined for the following modes (as applicable) on the airconditioner: (a) Off mode (where applicable). (b) Passive standby mode (where applicable). (c) Delay start mode (where applicable). (d) Average crank case heater power for various out

11、door conditions. Power in each applicable mode shall be reported in Watts to the nearest 0.1 W or better. 6.6.2 Off mode Where the air conditioner is not operational and where the air conditioner has no remote control or automatic program functions or these are inoperative. This mode is the lowest p

12、ower consumption mode that cannot be switched off (influenced) by the user and that persists for an indefinite time when an appliance is connected to the mains electricity supply and used in accordance with the manufacturers instructions. Measurements of crank case heaters (where present) shall be r

13、eported separately to this mode (see below) where possible. NOTE: Products may use some power in off mode to supply electronic controls. 6.6.3 Passive standby mode If present, where the airconditioner is not operational but where it has a remote control and/or is monitoring for a signal from a remot

14、e source or where there is a timer with some programming capability (e.g., timed or delay start). This mode includes those with remote communications capability where this facility is active. Where there are several possible power levels in this mode, the power for each shall be recorded with a desc

15、ription of its function. Measurements of crank case heaters (where present) shall be reported separately to this mode (see below) where possible. 6.6.4 Delay start mode If present, is where the model has a separate user option that is used to delay the commencement operation (only where this functio

16、n is not included as part of passive standby mode). 6.6.5 Crank case heaters Where an airconditioner has a crankcase heater (a small resistive heater attached to the compressor sump or crankcase (the sump is where oil and some refrigerant collects when the unit is not operating), the following readi

17、ngs shall be undertaken: (a) Average heater power (Watts) with the section containing the compressor under a dry bulb ambient temperature of 20 deg C +/2K. AMDT No. 3 FEB 2006 AMDT No. 3 FEB 2006 (b) Average heater power (Watts) with the section containing the compressor under a dry bulb ambient tem

18、perature of 7 deg C +/2K. Readings shall be measured over a period of not less than 3 hours. Where the heater exhibits any regular cyclic behaviour, a whole number of cycles shall be used to determine the average power. Where the ambient temperature does not influence the power consumption of the cr

19、ankcase heater the measurement may be conducted at any ambient temperature. Manufacturers may declare the values for (a) and (b) above based on measurements and knowledge of the control of the crankcase heater. For verification purposes a combination of analysis of the control system and measurement

20、s may be used to assess compliance, but a measurement at the specified conditions shall have precedence over any other method. 6.7 Testing airconditioners with variable output compressors Some types of variable output capacity air conditioners may require the setting of non-user accessible controls

21、to lock the output capacity at the rated capacity (or part load capacity) specified by the manufacturer. Where special tools or software are required to perform this function, the manufacturer shall provide the tools or software to the laboratory. For 50% part load performance testing, in the absenc

22、e of manufacturers information a compressor speed of 50% of the rated compressor speed may be used. Table 10 Delete the words from rating conditions from the heading in the third column and delete all symbols from 3rd column. Delete the figures 0.5oC (twice) from the 3rd column and replace with 0.6C

23、 (twice). Clause 9.1.2 Delete the text of the Clause and replace with the following: The values of standard capacities shall be expressed in kilowatts (which may be rounded to the nearest 0.01 kW) or watts (which may be rounded to the nearest 10 W). AMDT No. 3 FEB 2006 AMDT No. 3 FEB 2006 AMDT No. 3 FEB 2006 This page has been left blank intentionally.