1、 ATIS-0600307.2007 FIRE RESISTANCE CRITERIA - IGNITABILITY REQUIREMENTS FOR EQUIPMENT ASSEMBLIES, ANCILLARY NON-METALLIC APPARATUS, AND FIRE SPREAD REQUIREMENTS FOR WIRE AND CABLE A AMERICAN MERICAN N NATIONAL ATIONAL S STANDARD FOR TANDARD FOR T TELECOMMUNICATIONSELECOMMUNICATIONS The Alliance for

2、Telecommunication Industry Solutions (ATIS) is a technical planning and standards development organization that is committed to rapidly developing and promoting technical and operations standards for the communications and related information technologies industry worldwide using a pragmatic, flexib

3、le and open approach. Over 1,100 participants from over 300 communications companies are active in ATIS 22 industry committees and its Incubator Solutions Program. AMERICAN NATIONAL STANDARD Approval of an American National Standard requires review by ANSI that the requirements for due process, cons

4、ensus, and other criteria for approval have been met by the standards developer. Consensus is established when, in the judgment of the ANSI Board of Standards Review, substantial agreement has been reached by directly and materially affected interests. Substantial agreement means much more than a si

5、mple majority, but not necessarily unanimity. Consensus requires that all views and objections be considered, and that a concerted effort be made towards their resolution. The use of American National Standards is completely voluntary; their existence does not in any respect preclude anyone, whether

6、 he has approved the standards or not, from manufacturing, marketing, purchasing, or using products, processes, or procedures not conforming to the standards. The American National Standards Institute does not develop standards and will in no circumstances give an interpretation of any American Nati

7、onal Standard. Moreover, no person shall have the right or authority to issue an interpretation of an American National Standard in the name of the American National Standards Institute. Requests for interpretations should be addressed to the secretariat or sponsor whose name appears on the title pa

8、ge of this standard. CAUTION NOTICE: This American National Standard may be revised or withdrawn at any time. The procedures of the American National Standards Institute require that action be taken periodically to reaffirm, revise, or withdraw this standard. Purchasers of American National Standard

9、s may receive current information on all standards by calling or writing the American National Standards Institute. Notice of Disclaimer however, they must meet one of the other appropriate options contained in 4.1.2. See 4.1.1 and 4.1.2 regarding requirements for items such as plugs, sockets, jacks

10、, terminal blocks, etc., which may form part of an enclosure. Discrete (non-electrically energized) components with overall dimensions of 1/4 in (6.3 mm) x 1/4 in (6.3 mm) x 1/4 in (6.3 mm) or less, or constituting a fuel load of 1 g (0.035 oz) or less are exempt from the requirements of 4.1.2 and 4

11、.1.3. If such components are grouped in close proximity and their total mass exceeds 1 g (0.035 oz), they shall comply with 5.2. 4.1.4 Interconnect wire Individual interconnect wire and cable (copper and optic fiber) used within equipment assemblies shall satisfy the flammability requirements of VW-

12、1 as specified in ANSI/UL 1581. Any wire and cable exterior to an equipment assembly shall meet the requirements of 4.2. 4.2 Fire spread requirements for wire and cable The requirements in 4.2.1 through 4.2.3 apply to wire and cable, including communications cable, optical fiber cable, dc power wire

13、, and cable external to equipment assemblies. 5 -,-,- ATIS-0600307.2007 The requirements of 4.2 do not apply to OSP wire and cables. The requirements in 4.2.1 through 4.2.3 do not apply to compartmented cable entrance facilities. However, cables entering the CEF from the outside should be spliced to

14、 cables that comply with 4.2.1 through 4.2.3, as appropriate, as close as is practical to the point at which the cables enter the CEF. Wire and cable installations in hollow spaces, vertical shafts, and ventilation or air-handling ducts should be so made that the possible spread of fire or products

15、of combustion will not be substantially increased. All penetrations through fire-resistance rated walls, partitions, floors, or ceilings should be fire stopped using products tested to ANSI/UL 1479 (ASTM E 814), the requirements of the fire stop manufacturer and the requirements of the local model b

16、uilding code in force. 4.2.1 Ducts, plenums, or other space used for conditioned air Communications wire and cable shall have a maximum flame spread of 5 ft (1.52 m), a maximum peak optical density of 0.5, and a maximum average optical density of 0.15, when tested in accordance with ANSI/NFPA 262. E

17、xamples of cable types meeting these requirements are: CMP, CL2P, CL3P, OFNP, OFCP, MPP, FPLP, and CATVP. Power wire and cable shall comply with Article 300-22 of ANSI/NFPA 70. 4.2.2 Riser shafts Wire and cable in riser shafts shall comply with the requirements of ANSI/UL 1666. Examples of cable typ

18、es meeting these requirements are: CMR, CL2R, CL3R, OFNR, OFCR, MPR, FPLR, and CATVR, in addition to those specified in 4.2.1. 4.2.3 Other spaces Wire and cable used in spaces other than those covered by 4.2.1 and 4.2.2 shall comply with the requirements of the vertical-tray flame test per one of th

19、e following: UL 1685; CAN/CSA-C22.2 No. 0.3; or ANSI/IEEE 1202. Examples of cable types meeting these requirements are: CM, CL2, CL3, OFN, OFC, MP, FPL, and CATV, in addition to those specified in 4.2.1 and 4.2.2. 4.2.4 AC-Powered Wiring and Fittings All wiring, fittings, and fixtures used for AC po

20、wer shall meet the requirements for flammability per NFPA 70 (NEC) based on their application. 6 ATIS-0600307.2007 4.3 Fire spread requirements for optical fiber cable trays or raceways. The requirements in 4.3.1 through 4.3.3 apply to optical fiber cable trays or raceways constructed of combustible

21、 materials and external to equipment assemblies. All optical fiber cable trays or raceways shall meet the applicable fire resistance requirements of ANSI/NFPA 70. The requirements in 4.3.1 through 4.3.3 do not apply to compartmented cable entrance facilities. However, optical fiber cable trays enter

22、ing the CEF from the outside should be jointed to optical fiber cable trays/raceways that comply with 4.3.1 through 4.3.3, as appropriate, as close as is practical to the point at which the cables enter the CEF. Optical fiber cable tray/raceway installations in hollow spaces, vertical shafts, and ve

23、ntilation or air- handling ducts should be so made that the possible spread of fire or products of combustion will not be substantially increased. All penetrations through fire-resistance-rated walls, partitions, floors, or ceilings should be fire stopped using products tested to ASTM E 814 (ANSI/UL

24、 1479), the requirements of the fire stop manufacturer and the requirements of the local model building code in force. 4.3.1 Ducts, plenums, or other space used for conditioned air Optical fiber cable tray/raceway shall have a maximum flame spread of 5 ft (1.52 m), a maximum peak optical density of

25、0.5, and a maximum average optical density of 0.15, when tested in accordance with the Test For Flame Propagation and Smoke-Density Values (Plenum) ANSI/UL 2024A. A raceway marked “Plenum“ is suitable for use in ducts, plenums, or other spaces used for environmental air in accordance with Sections 7

26、70-53(a) and 800-53(a) of the National Electrical Code when used to enclose optical fiber cables marked OFNP or communications cable marked CMP or CMP-OF. A raceway marked “Plenum“ is also suitable for installation in risers when used to enclose optical fiber cables marked OFNP or OFNR, or communica

27、tions cables marked CMP, CMP-OF, CMR, or CMR-OF and general purpose use when used to enclose optical fiber cables marked OFNP, OFNR, OFNG, or OFN or communications cables marked CMP, CMP-OF, CMR, CMR-OF, CMG, CMG-OF, CM, or CM-OF. 4.3.2 Riser shafts Optical fiber cable tray/raceway in riser shafts s

28、hall comply with the requirements of the Test for Flame Propagation (Riser) in UL 2024A. A raceway marked “Riser“ is suitable for installation in risers in accordance with Sections 770-53(b) and 800-53(b) of the National Electrical Code when used to enclose optical fiber cable marked OFNP and OFNR o

29、r communications cable marked CMP, CMP-OF, CMR, or CMR-OF. This raceway has fire resistant characteristics capable of preventing the carrying of fire from floor to floor. This raceway is identified by a marking on the surface of the raceway or on a marker tape indicating “Riser.” A raceway marked “R

30、iser“ is also suitable for general-purpose use when used to enclose optical fiber cable marked OFNP, OFNR, OFNG, or OFN or communications cable marked CMP, CMP-OF, CMR, CMR-OF, CMG, CMG-OF, CM, and CM-OF. 7 ATIS-0600307.2007 4.3.3 Other spaces Optical fiber cable tray/raceway used in spaces other th

31、an those covered by 4.3.1 and 4.3.2 shall comply with the requirements of the vertical-tray flame test (general use) per ANSI/UL 2024A. A raceway with neither the marking “Plenum“ nor “Riser“ is suitable for general purpose use, with the exception of risers, plenums, and other spaces used for enviro

32、nmental air when used to enclose optical fiber cables marked OFNP, OFNR, or OFN or communications cables marked CMG, CMG-OF, CM, CM-OF, CMR, CMR-OF, CMP, or CMP-OF. 4.4 Ignitability requirements for ancillary materials Exposed nonmetallic apparatus such as framework components, protective covers, vi

33、ewing panels, etc., shall comply with the following as is applicable: a) Products having an exposed surface area 1 ft.2 (0.09 m2) shall be formed from materials having a fire resistance characteristic equivalent to or better than UL-94 V-0 at its minimum rated thickness. b) Products having an expose

34、d surface area 1 ft.2 (0.09 m2) to 10 ft.2 (0.93 m2) shall be formed from materials having a fire resistance characteristic equivalent to or better than UL-94 5VA at its minimum rated thickness. c) Products having an exposed surface area 10 ft.2 (0.93 m2) shall be formed from materials having a fire

35、 resistance characteristic equivalent to or better than UL-94 5VA at its minimum rated thickness, and shall have a flame spread rating of 1750 (V 0.107) 30 Note: If V is 2500 mm3 (0.15 i3) only IEC 60695-11-5 may be utilized Table 2 - Performance criteria for the ANSI/UL1694 needle flame test Criter

36、ia Conditions SC-0 SC-1 SC-TC 0 SC-TC 1 Individual after flame (sec) 10 30 10 30 Total time after flame (sec)* 50 / 30 250 / 150 50 / 30 250 / 150 Individual after flame + after glow (sec) 30 60 30 60 Ignition of indicator? No No No No Complete consumption? No No Yes Yes NOTES: SC denotes small component. TC denotes total consumption. * Total after flame: first value is based on 5 applications of the ignition source; the second value is based on 3 applications of the ignition source. 9