1、BRITISH STANDARD BS EN 1366-3:2004 Fire resistance tests for service installations Part 3: Penetration seals The European Standard EN 1366-3:2004 has the status of a British Standard ICS 13.220.50 ? Licensed Copy: sheffieldun sheffieldun, na, Sun Oct 29 09:35:37 GMT+00:00 2006, Uncontrolled Copy, (c

2、) BSI BS EN 1366-3:2004 This British Standard was published under the authority of the Standards Policy and Strategy Committee on 8 September 2004 BSI 8 September 2004 ISBN 0 580 44420 1 National foreword This British Standard is the official English language version of EN 1366-3:2004. The UK partic

3、ipation in its preparation was entrusted by Technical Committee FSH/22, Fire resistance tests, to Subcommittee FSH/22/3, Fire penetration seals, which has the responsibility to: A list of organizations represented on this subcommittee can be obtained on request to its secretary. Cross-references The

4、 British Standards which implement international or European publications referred to in this document may be found in the BSI Catalogue under the section entitled “International Standards Correspondence Index”, or by using the “Search” facility of the BSI Electronic Catalogue or of British Standard

5、s Online. This publication does not purport to include all the necessary provisions of a contract. Users are responsible for its correct application. Compliance with a British Standard does not of itself confer immunity from legal obligations. aid enquirers to understand the text; present to the res

6、ponsible international/European committee any enquiries on the interpretation, or proposals for change, and keep the UK interests informed; monitor related international and European developments and promulgate them in the UK. Summary of pages This document comprises a front cover, an inside front c

7、over, the EN title page, pages 2 to 38, an inside back cover and a back cover. The BSI copyright notice displayed in this document indicates when the document was last issued. Amendments issued since publication Amd. No. DateComments Licensed Copy: sheffieldun sheffieldun, na, Sun Oct 29 09:35:37 GM

8、T+00:00 2006, Uncontrolled Copy, (c) BSI EUROPEAN STANDARD NORME EUROPENNE EUROPISCHE NORM EN 1366-3 September 2004 ICS 13.220.50 English version Fire resistance tests for service installations - Part 3: Penetration seals Essais de rsistance au feu des installations techniques - Partie 3: Calfeutrem

9、ents Feuerwiderstandsprfungen fr Installationen - Teil 3: Abschottungen This European Standard was approved by CEN on 3 March 2004. CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national stan

10、dard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the Central Secretariat or to any CEN member. This European Standard exists in three official versions (English, French, German). A version in any other l

11、anguage made by translation under the responsibility of a CEN member into its own language and notified to the Central Secretariat has the same status as the official versions. CEN members are the national standards bodies of Austria, Belgium, Cyprus, Czech Republic, Denmark, Estonia, Finland, Franc

12、e, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom. EUROPEAN COMMITTEE FOR STANDARDIZATION COMIT EUROPEN DE NORMALISATION EUROPISCHES KOMITEE FR NORMUNG M

13、anagement Centre: rue de Stassart, 36 B-1050 Brussels 2004 CENAll rights of exploitation in any form and by any means reserved worldwide for CEN national Members. Ref. No. EN 1366-3:2004: E Licensed Copy: sheffieldun sheffieldun, na, Sun Oct 29 09:35:37 GMT+00:00 2006, Uncontrolled Copy, (c) BSI EN

14、1366-3: 2004 (E) 2 Contents Foreword4 Introduction .5 1 Scope.6 2 Normative references 6 3 Terms and definitions7 4 Test equipment.8 5 Test conditions.8 5.1 Heating conditions.8 5.2 Pressure conditions.8 6 Test specimen 8 6.1 General8 6.2 Size8 6.3 Number8 6.4 Design .9 6.4.1 General9 6.4.2 Support

15、conditions for penetrating services9 6.4.3 Pipe end configuration9 6.4.4 Cable end configuration10 6.4.5 Blank penetration seal.10 6.4.6 Subsequent addition of services10 6.5 Construction.10 6.6 Verification10 7 Installation of test specimen.10 7.1 General10 7.2 Supporting construction.10 7.2.1 Gene

16、ral10 7.2.2 Standard supporting constructions.11 7.3 Installation of service 12 7.4 Installation of penetration seal.12 7.5 Multiple test specimens.13 8 Conditioning.13 9 Application of instrumentation.13 9.1 Thermocouples 13 9.1.1 Furnace thermocouples (plate thermometers) .13 9.1.2 Unexposed face

17、thermocouples.13 9.1.3 Roving thermocouple14 9.2 Integrity measurement.14 9.3 Pressure14 10 Test procedure .15 10.1 General15 10.2 Integrity.15 10.3 Insulation 15 10.4 Other observations15 11 Performance criteria15 11.1 Integrity.15 11.2 Insulation 15 11.3 Multiple penetrations.15 Licensed Copy: she

18、ffieldun sheffieldun, na, Sun Oct 29 09:35:37 GMT+00:00 2006, Uncontrolled Copy, (c) BSI EN 1366-3:2004 (E) 3 12 Test report 15 13 Field of direct application of test results.16 Annex A (informative) Explanatory notes .21 A.1 General21 A.2 Notes on the scope and application of test results21 A.3 Not

19、es on test conditions.22 A.4 Notes on test construction .22 A.5 Suggested pipe end configurations for different end-uses.23 A.6 Notes on test procedure23 A.7 Notes on test criteria .23 A.8 Notes on validity of test results23 A.9 Notes on test report.24 A.10 Small diameter control cables24 Annex B (n

20、ormative) Standard configuration for cable penetration seals 25 B.1 Structure of specimens.25 B.2 Deviations from standard specimens26 B.3 Field of direct application26 Annex C (normative) Standard configuration and field of direct application for penetration seals for pipes35 C.1 Standard configura

21、tion for penetration seals for metal pipes35 C.2 Non-standard configurations36 C.3 Direct field of application37 Licensed Copy: sheffieldun sheffieldun, na, Sun Oct 29 09:35:37 GMT+00:00 2006, Uncontrolled Copy, (c) BSI EN 1366-3: 2004 (E) 4 Foreword This document (EN 1366-3:2004) has been prepared

22、by Technical Committee CEN /TC 127 “Fire safety in buildings”, the secretariat of which is held by BSI. This European Standard shall be given the status of a national standard, either by publication of an identical text or by endorsement, at the latest by March 2005, and conflicting national standar

23、ds shall be withdrawn at the latest by March 2005. This document has been prepared under a mandate given to CEN by the European Commission and the European Free Trade Association. According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following countries are b

24、ound to implement this European Standard : Austria, Belgium, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Slovakia, Slovenia, Spain, Sweden, Switzerland and U

25、nited Kingdom. EN 1366 Fire resistance tests for service installations consists of the following: Part 1: Ducts Part 2: Fire dampers Part 3: Penetration seals Part 4: Linear joint seals (in course of preparation) Part 5: Service ducts and shafts Part 6: Raised access floors and hollow floors (in cou

26、rse of preparation) Part 7: Closures for conveyors and trackbound transportation systems (in course of preparation) Part 8: Smoke extraction ducts Part 9: Single compartment smoke extraction ducts (in course of preparation) Part 10: Smoke control dampers (in course of preparation) Licensed Copy: she

27、ffieldun sheffieldun, na, Sun Oct 29 09:35:37 GMT+00:00 2006, Uncontrolled Copy, (c) BSI EN 1366-3:2004 (E) 5 Introduction This document has been prepared to provide a method of test for assessing the contribution of a penetration sealing system to the fire resistance of separating elements when the

28、y have been penetrated by a service or services. CAUTION The attention of all persons concerned with managing and carrying out this fire resistance test is drawn to the fact that fire testing may be hazardous and that there is a possibility that toxic and/or harmful smoke and gases may be evolved du

29、ring the test. Mechanical and operational hazards may also arise during the construction of the test elements or structures, their testing and disposal of test residues. An assessment of all potential hazards and risks to health should be made and safety precautions should be identified and provided

30、. Written safety instructions should be issued. Appropriate training should be given to relevant personnel. Laboratory personnel should ensure that they follow written safety instructions at all times. Licensed Copy: sheffieldun sheffieldun, na, Sun Oct 29 09:35:37 GMT+00:00 2006, Uncontrolled Copy,

31、 (c) BSI EN 1366-3: 2004 (E) 6 1 Scope This document specifies a method of test and criteria for the evaluation of the ability of a penetration sealing system to maintain the fire resistance of a separating element at the position at which it has been penetrated by a service. Excluded are chimneys,

32、air ventilation systems, fire rated ventilation ducts, fire rated service ducts, shafts and smoke extraction ducts. Supporting constructions are used in this document to represent separating elements such as walls or floors. These simulate the interaction between the test specimen and the separating

33、 element into which the sealing system is to be installed in practice. This document is used in conjunction with EN 1363-1. The purpose of this test described in this document is to assess: a) the effect of such penetrations on the integrity and insulation performance of the separating element conce

34、rned; b) the integrity and insulation performance of the penetration sealing system; c) the insulation performance of the penetrating service or services, and where necessary, the integrity failure of a service. No information can be implied by the test concerning the influence of the inclusion of s

35、uch penetrations and sealing systems on the loadbearing capacity of the separating element. It is not the intention of this test to provide quantitative information on the rate of leakage of smoke and/or hot gases or on the transmission or generation of fumes. Such phenomena should only be noted in

36、describing the general behaviour of test specimens during the test. This test does not supply any information on the ability of the penetration sealing system to withstand stress caused by movements or displacements of the penetrating services. Explanatory notes to this test method are given in Anne

37、x A. 2 Normative references The following referenced documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. prEN 520, Gypsum plas

38、terboards Definitions, requirements and test methods. EN 1363-1:1999, Fire resistance tests Part 1: General requirements. EN 1363-2, Fire resistance tests Part 2: Alternative and additional procedures. EN 10025, Hot rolled products of non-alloy structural steels - Technical delivery conditions. EN I

39、SO 13943:2000, Fire safety Vocabulary (ISO 13943:2000). HD 21.3 S3: 1995, Polyvinyl chloride insulated cables of rated voltages up to and including 450/750V Part 3: Non-sheathed cables for fixed wiring (IEC 60227-3:1993, modified). Licensed Copy: sheffieldun sheffieldun, na, Sun Oct 29 09:35:37 GMT+

40、00:00 2006, Uncontrolled Copy, (c) BSI EN 1366-3:2004 (E) 7 HD 22.4 S3: 1995, Rubber insulated cables of rated voltages up to and including 450/750V Part 4: Cords and flexible cables (IEC 60245-4:1994, modified). HD 22.7 S2: 1995, Rubber insulated cables of rated voltages up to and including 450/750

41、V Part 7: Cables with increased heat resistance for internal wiring for a conductor temperature of 110 C. HD 22.9 S2: 1995, Rubber insulated cables of rated voltages up to and including 450/750V Part 9: Single core non-sheathed cables for fixed wiring having low emission of smoke and corrosive gases

42、. 3 Terms and definitions For the purposes of this document, the terms and definitions given in EN 1363-1:1999 and EN ISO 13943:2000 and the following apply. 3.1 penetration aperture in a separating element for the passage of one or more services 3.2 service system such as a cable, conduit, pipe (wi

43、th or without insulation), or trunking 3.3 penetration seal system used to maintain the fire resistance of a separating element at the position where there is provision for services to pass through the separating element 3.4 penetration sealing system assembly for test consisting of the penetrating

44、service or services and the penetration seal, materials or devices, together with any service supporting construction, designed to maintain the integrity and insulation performance of the separating element for the duration of the fire test 3.5 service support construction mechanical support provide

45、d in the form of clips, ties, hangers, ladder racks or trays, or any device designed to carry the load of the penetrating services 3.6 standard supporting construction form of construction of known fire resistance used to close off the furnace and support the penetration sealing system being evaluat

46、ed 3.7 blank penetration seal aperture of specified size in the separating element which is sealed or closed by the specified seal without incorporation of penetrating services 3.8 flexible construction horizontal or vertical supporting construction consisting of studs or joists, including linings a

47、nd optional insulation Licensed Copy: sheffieldun sheffieldun, na, Sun Oct 29 09:35:37 GMT+00:00 2006, Uncontrolled Copy, (c) BSI EN 1366-3: 2004 (E) 8 4 Test equipment In addition to the test equipment specified in EN 1363-1, and if applicable EN 1363-2, the minimum internal dimensions of the furna

48、ce shall be 1 m 1 m 1 m. 5 Test conditions 5.1 Heating conditions The heating conditions and the furnace atmosphere shall conform to those given in EN 1363-1 or, if applicable, EN 1363-2. 5.2 Pressure conditions 5.2.1 Pressure conditions shall be as given in EN 1363-1. 5.2.2 Where there is only a si

49、ngle vertical penetration that has a maximum height of 1 m, a pressure of (15 2) Pa shall be established at the centre of this penetration. 5.2.3 If a single vertical penetration sealing system is tested which has a height of more than 1 m, it shall be tested with a pressure of (20 2) Pa at its top and in such cases penetrating services shall be included in the zone where positive pressure exceeds 10 Pa (see Figure 1). 5.2.4 If more than one penetration sealing systems is tes