《BS-EN-60896-22-2004.pdf》由会员分享,可在线阅读,更多相关《BS-EN-60896-22-2004.pdf(32页珍藏版)》请在三一文库上搜索。
1、BRITISH STANDARD BS EN 60896-22:2004 Stationary lead-acid batteries Part 22: Valve regulated types Requirements The European Standard EN 60896-22:2004 has the status of a British Standard ICS 29.220.20 ? Licensed Copy: sheffieldun sheffieldun, na, Fri Nov 10 15:08:12 GMT+00:00 2006, Uncontrolled Cop
2、y, (c) BSI BS EN 60896-22:2004 This British Standard was published under the authority of the Standards Policy and Strategy Committee on 16 March 2005 BSI 16 March 2005 ISBN 0 580 45584 X National foreword This British Standard is the official English language version of EN 60896-22:2004. It is iden
3、tical with IEC 60896-22:2004. The UK participation in its preparation was entrusted to Technical Committee PEL/21, Secondary cells and batteries, which has the responsibility to: A list of organizations represented on this committee can be obtained on request to its secretary. Cross-references The B
4、ritish Standards which implement international or European publications referred to in this document may be found in the BSI Catalogue under the section entitled “International Standards Correspondence Index”, or by using the “Search” facility of the BSI Electronic Catalogue or of British Standards
5、Online. This publication does not purport to include all the necessary provisions of a contract. Users are responsible for its correct application. Compliance with a British Standard does not of itself confer immunity from legal obligations. aid enquirers to understand the text; present to the respo
6、nsible international/European committee any enquiries on the interpretation, or proposals for change, and keep the UK interests informed; monitor related international and European developments and promulgate them in the UK. Summary of pages This document comprises a front cover, an inside front cov
7、er, the EN title page, pages 2 to 29 and a back cover. The BSI copyright notice displayed in this document indicates when the document was last issued. Amendments issued since publication Amd. No. DateComments Licensed Copy: sheffieldun sheffieldun, na, Fri Nov 10 15:08:12 GMT+00:00 2006, Uncontroll
8、ed Copy, (c) BSI EUROPEAN STANDARD EN 60896-22 NORME EUROPENNE EUROPISCHE NORM March 2004 CENELEC European Committee for Electrotechnical Standardization Comit Europen de Normalisation Electrotechnique Europisches Komitee fr Elektrotechnische Normung Central Secretariat: rue de Stassart 35, B - 1050
9、 Brussels 2004 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members. Ref. No. EN 60896-22:2004 E ICS 29.220.20 English version Stationary lead-acid batteries Part 22: Valve regulated types Requirements (IEC 60896-22:2004) Batteries stationnaires au
10、 plomb Part 22: Types tanches soupapes - Exigences (CEI 60896-22:2004) Ortsfeste Blei-Akkumulatoren Teil 22: Verschlossene Bauarten - Anforderungen (IEC 60896-22:2004) This European Standard was approved by CENELEC on 2004-03-01. CENELEC members are bound to comply with the CEN/CENELEC Internal Regu
11、lations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the Central Secretariat or to any CENELEC member. Th
12、is European Standard exists in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CENELEC member into its own language and notified to the Central Secretariat has the same status as the official versions. CENELEC membe
13、rs are the national electrotechnical committees of Austria, Belgium, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Slovakia, Slovenia, Spain, Sweden, Switzerla
14、nd and United Kingdom. Licensed Copy: sheffieldun sheffieldun, na, Fri Nov 10 15:08:12 GMT+00:00 2006, Uncontrolled Copy, (c) BSI EN 69806-2202:40 - - 2 Foreword The text of document 21/595/FDIS, future edition 1 of IEC 60896-22, prepared by IEC TC 21, Secondary cells and batteries, was submitted to
15、 the IEC-CENELEC parallel vote and was approved by CENELEC as EN 60896-22 on 2004-03-01. The following dates were fixed: latest date by which the EN has to be implemented at national level by publication of an identical national standard or by endorsement (dop) 2004-12-01 latest date by which the na
16、tional standards conflicting with the EN have to be withdrawn (dow) 2007-03-01 Annex ZA has been added by CENELEC. _ Endorsement notice The text of the International Standard IEC 60896-22:2004 was approved by CENELEC as a European Standard without any modification. In the official version, for Bibli
17、ography, the following notes have to be added for the standards indicated: IEC 60050-826 NOTE Harmonized as HD 384.2 S1:1986 (not modified). IEC 60068-2-32 NOTE Harmonized as EN 60068-2-32:1993 (not modified). IEC 60095 NOTE Harmonized in EN 60095 series (partly modified). IEC 60359 NOTE Harmonized
18、as EN 60359:2002 (not modified). IEC 60695-11-10 NOTE Harmonized as EN 60695-11-10:1999 (not modified). IEC 60707 NOTE Harmonized as EN 60707:1999 (not modified) IEC 60950-1 NOTE Harmonized as EN 60950-1:2001 (modified). IEC 61056 NOTE Harmonized in EN 61056 series (not modified). IEC 61427 NOTE Har
19、monized as EN 61427:2001 (not modified). ISO 9000 NOTE Harmonized as EN ISO 9000:2000 (not modified). ISO 9001 NOTE Harmonized as EN ISO 9001:1994 (not modified). ISO 9001 NOTE Harmonized as EN ISO 9001:2000 (not modified). _ Page 2 EN 6089622:2004 Licensed Copy: sheffieldun sheffieldun, na, Fri Nov
20、 10 15:08:12 GMT+00:00 2006, Uncontrolled Copy, (c) BSI 068-6922 CEI:0240 3 CONTENTS OFREWODR.5 1 Scope.4 2 Normative references .4 3 Terms and definitions .4 4 Functional requirements .10 5 Reporting format.12 6 Requirements and characteristics.13 Annex A (normative) User statement of requirements
21、25 Annex B (normative) Supplier statement of product range test results26 Bibilogrpahy Tlbae 1 Safe orepatior neuqrimenest .12 Tabl 2 e ePrformance riuqeremetns . Telba 3 Duratiliby reuqirmestne .32 Tlbae 4 Requrimenef tor sag mesisino fniormitaon Tlbae 5 Requrimenef tor high current toleracne. Tlba
22、e 6 Requrimenef tor sroh-tcirciuc turrent and c.d. niternal resistance fniormtaoin. TabluqeR 7 eirement ofr pretocoitn iaganst nietrlan iingnoit rfom exetrnaps lark 13 TabluqeR 8 eirement ofr pretocoitn iaganst grous dnhorrp teponstiy 13 TabluqeR 9 eirement ofr coetnnt naud drabtiliy of iuqerm derak
23、rings eRiuqrement )a 33 Tabl01 e qeR uirement ofr tnocnet and udrailibty of ruqeirde markings iuqeRremetn b).33 Tlbae 11 Reuqrimetne for maretial identficiatoin 53 Tlbae 12 Reuqrimetne for the poretaion fo the valve 53 Tlbae 13 Reuqrimetne for definition fo thf elmamibality rating fo htm eaterials .
24、53 Tlbae 14 Reuqrimetne for perfromcnae fo hte niretcelc lonncerot.73 Tlbae 15 Reuqrimetne for discharge capacity perfromcnae 73 Tlbae 16 Reuqrimetne for chraeg retetnion durign stroage.93 Tlbae 17 Reuqrimetne for flaos tervcie iwth daily dischargse .93 Tlbae 18 Reuqrimetne for rechraeg behavioru14
25、Tlbae 19 Reuqrimetne for servcil eife at an oreptainmet gpreatrue fo 04 C 14 Tlbae 20 Reuqrimetne for the micapt fo a stress metpretarue fo 55 o Cr 06 C.9 Tlbae 21 Reuqrimetne for the micapt fo abusive ovre-dischrages. Tabl22 e qeR uirementf sor inofrmatnoi on ehtrmar lwanuay sensitivity.54 Tlbae 23
26、 Reuqrimetne for the micapt fo low metperatrue servcie on cacaptiy.74 Tlbae 24 Reuqrimetne for dimsneioanl stbaility at elevatde niternal rpsesures and metrepatruse 74 Tabl52 e R equirementrof s batstiliy aniagsm tehcinacal abuse of inuts udgnir installaoitn.49 Page 3 EN 6089622:2004 60896-22 IEC:20
27、04 3 TNOCENTS OFREWODR.5 1Scope.9 2Nromative referecnse .9 3Trems dna definiitons .9 4Functional reuqrimenest .12 5 Reporting formta.25 6 Requrimenest and chracateristcis.72 Annex A (nromative) sUer statmeent of reuqrimentes 72 Annex B (nromative) Supplier sttametne fo rpocudr tagne test resustl35 B
28、ibliography28 Table 1 Safe operation requirements .10 Table 2 Performance requirements 11 Table 3 Durability requirements .11 Table 4 Requirement for gas emission information.13 Table 5 Requirement for high current tolerance14 Table 6 Requirement for short-circuit current and d.c. internal resistanc
29、e information.14 Table 7 Requirement for protection against internal ignition from external spark sources15 Table 8 Requirement for protection against ground short propensity 15 Table 9 Requirement for content and durability of required markings Requirement a) 16 Table 10 Requirement for content and
30、 durability of required markings Requirement b).16 Table 11 Requirement for material identification 17 Table 12 Requirement for the operation of the valve 17 Table 13 Requirement for definition of the flammability rating of the materials .17 Table 14 Requirement for performance of the intercell conn
31、ector.18 Table 15 Requirement for discharge capacity performance 18 Table 16 Requirement for charge retention during storage.19 Table 17 Requirement for float service with daily discharges .19 Table 18 Requirement for recharge behaviour20 Table 19 Requirement for service life at an operating tempera
32、ture of 40 C 20 Table 20 Requirement for the impact of a stress temperature of 55 C or 60 C.21 Table 21 Requirement for the impact of abusive over-discharges.22 Table 22 Requirements for information on thermal runaway sensitivity.22 Table 23 Requirement for the impact of low temperature service on c
33、apacity.23 Table 24 Requirement for dimensional stability at elevated internal pressures and temperatures 23 Table 25 Requirements for stability against mechanical abuse of units during installation.24 3 egaP 4002:2269806 NE Annex ZA (normative) Normative references to international publications wit
34、h their corresdnopiuE gnroepap nublicatsnoi . 15 Annex ZA (normative) Normative references to international publications with their corresponding European publications . 27 Licensed Copy: sheffieldun sheffieldun, na, Fri Nov 10 15:08:12 GMT+00:00 2006, Uncontrolled Copy, (c) BSI 068-6922 CEI:0240 9
35、STATIONARY LEAD-ACID BATTERIES Part 22: Valve regulated types Requirements 1 Scope This part of IEC 60896 applies to all stationary lead-acid cells and monobloc batteries of the valve regulated type for float charge applications, (i.e. permanently connected to a load and to a d.c. power supply), in
36、a static location (i.e. not generally intended to be moved from place to place) and incorporated into stationary equipment or installed in battery rooms for use in telecom, uninterruptible power supply (UPS), utility switching, emergency power or similar applications. The objective of this part of I
37、EC 60896 is to assist the specifier in the understanding of the purpose of each test contained within IEC 60896-21 and provide guidance on a suitable requirement that will result in the battery meeting the needs of a particular industry application and operational condition. This standard is used in
38、 conjunction with the common test methods described in IEC 60896-21 and is associated with all types and construction of valve regulated stationary lead-acid cells and monoblocs used in standby power applications. This part of IEC 60896 does not apply to lead-acid cells and batteries used for vehicl
39、e engine starting applications (IEC 60095 series), solar photovoltaic applications (IEC 61427), or general purpose applications (IEC 61056 series). 2 Normative references The following referenced documents are indispensable for the application of this document. For dated references, only the edition
40、 cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. IEC 60896-21:2004, Stationary lead-acid batteries Part 21: Valve regulated types Methods of test) ISO 1043-1, Plastics Symbols and abbreviated terms Part 1: Basic polymers and th
41、eir special characteristics 3 Terms and definitions For the purposes of this document, the following definitions apply. 3.1 accuracy (of a measuring instrument) quality which characterizes the ability of a measuring instrument to provide an indicated value close to a true value of the measurand IEV
42、311-06-08 NOTE Accuracy is all the better when the indicated value is closer to the corresponding true value. Page 4 EN 6089622:2004 Licensed Copy: sheffieldun sheffieldun, na, Fri Nov 10 15:08:12 GMT+00:00 2006, Uncontrolled Copy, (c) BSI 068-6922 CEI:0240 11 3.2 accuracy class category of measurin
43、g instruments, all of which are intended to comply with a set of specifications regarding uncertainty IEV 311-06-09 3.3 ambient temperature temperature of the medium in the immediate vicinity of a cell or battery IEV 486-03-12 3.4 ampere-hour quantity of electricity or a capacity of a battery obtain
44、ed by integrating the discharge current in ampere with respect to time in hours NOTE One ampere-hour equals 3 600 coulombs. 3.5 secondary battery two or more secondary cells connected together and used as a source of electrical energy IEV 486-01-03 3.6 monobloc battery secondary battery in which the
45、 plate packs are fitted in a multi-compartment container IEV 486-01-17 3.7 floating battery secondary battery whose terminals are permanently connected to a source of constant voltage sufficient to maintain the battery approximately fully charged, intended to supply a circuit, if the normal supply i
46、s temporarily interrupted IEV 486-04-10 3.8 battery capacity quantity of electricity or electrical charge which a fully charged battery can deliver under specified conditions NOTE The SI unit for electric charge is the coulomb (1 C = 1 A.s) but in practice, battery capacity is expressed in ampere-ho
47、urs (Ah). IEV 486-03-01 3.9 charge operation during which a secondary battery receives from an external circuit electrical energy, which is converted into chemical energy IEV 486-01-11 NOTE A charge is defined by its maximum voltage, current and duration. Page 5 EN 6089622:2004 Licensed Copy: sheffi
48、eldun sheffieldun, na, Fri Nov 10 15:08:12 GMT+00:00 2006, Uncontrolled Copy, (c) BSI 068-6922 CEI:0240 31 3.10 full charge state where all the available active material of a secondary cell or battery has been reconverted to its fully charged status IEV 486-03-37 3.11 overcharge continued charging a
49、fter the full charge of a secondary cell or battery IEV 486-03-35 3.12 cell assembly of electrodes and electrolyte, which constitutes the basic unit of a secondary battery IEV 486-01-02 3.13 electrochemical cell electrochemical system capable of storing in chemical form the electric energy received and which c