1、HARMONIZATION DOCUMENT HD 22.4 S4 DOCUMENT DHARMONISATION HARMONISIERUNGSDOKUMENT March 2004 CENELEC European Committee for Electrotechnical Standardization Comit Europen de Normalisation Electrotechnique Europisches Komitee fr Elektrotechnische Normung Central Secretariat: rue de Stassart 35, B - 1

2、050 Brussels 2004 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members. Ref. No. HD 22.4 S4:2004 E ICS 29.060.20 Supersedes HD 22.4 S3:1995 + A1:1999 + A2:2002 English version Cables of rated voltages up to and including 450/750 V and having crossl

3、inked insulation Part 4: Cords and flexible cables Conducteurs et cbles isols avec des matriaux rticuls de tension assigne au plus gale 450/750 V Partie 4: Cbles souples Starkstromleitungen mit vernetzter Isolierhlle fr Nennspannungen bis 450/750 Teil 4: Flexible Leitungen This Harmonization Documen

4、t was approved by CENELEC on 2004-02-01. CENELEC members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for implementation of this Harmonization Document on a national level. Up-to-date lists and bibliographical references concerning such national implem

5、entation may be obtained on application to the Central Secretariat or to any CENELEC member. This Harmonization Document exists in three official versions (English, French, German). CENELEC members are the national electrotechnical committees of Austria, Belgium, Cyprus, Czech Republic, Denmark, Est

6、onia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom. HD 22.4 S4:2004 - 2 - Foreword This edition 4 of HD 22.4 has been prepared by Tech

7、nical Committee CLC/TC 20, Electric cables. It provides a full updating of edition 3, including incorporation of amendment No 1, and introduces other improvements. HD 22.4 S4 is related to IEC 60245-4 (1994), but is not directly equivalent. HD 22 now has the following parts: HD 22.1 S4 - General req

8、uirements HD 22.2 S3 - Test methods HD 22.3 S4 - Heat resistant silicone rubber insulated cables HD 22.4 S4 - Cords and flexible cables HD 22.5 - (Spare) HD 22.6 S2 - Arc welding cables HD 22.7 S2 - Cables with increased heat resistance for internal wiring for a conductor temperature of 110 C HD 22.

9、8 S2 - Polychloroprene or equivalent synthetic elastomer sheathed cable for use as decorative chains HD 22.9 S2 - Single core non-sheathed cables for fixed wiring having low emission of smoke and corrosive gases HD 22.10 S1 - EPR insulated and polyurethane sheathed flexible cables HD 22.11 S1 - EVA

10、cords and flexible cables HD 22.12 S1 - Heat resistant EPR cords and flexible cables HD 22.13 S1 - Single and multicore flexible cables, insulated and sheathed with crosslinked compound and having low emission of smoke and corrosive gases HD 22.14 S2 - Cords for applications requiring high flexibili

11、ty HD 22.15 S1 - Multicore cables insulated and sheathed with heat resistant silicone rubber HD 22.16 S1 - Water resistant polychloroprene or equivalent elastomer sheathed flexible cables The draft Harmonisation Document was submitted to the Unique Acceptance Procedure and approved by CENELEC as HD

12、22.4 S4 on 2004-02-01. The following dates were fixed: - latest date by which the existence of the HD has to be announced at national level (doa) 2004-08-01 - latest date by which the EN has to be implemented at national level by publication of a harmonised national standard or by endorsement (dop)

13、2005-02-01 - latest date by which the national standards conflicting with the HD have to be withdrawn (dow) 2006-02-01 - 3 - HD 22.4 S4:2004 Contents Page 1 Scope 4 2 Normative references . 4 3 Ordinary EPR insulated and EPR sheathed cord and flexible cable . 4 3.1 Code designation. 4 3.2 Rated volt

14、age 4 3.3 Construction 5 3.4 Tests. 5 3.5 Guide to use (informative) 5 4 Ordinary polychloroprene or other equivalent synthetic elastomer sheathed cord and flexible cable . 8 4.1 Code designation. 8 4.2 Rated voltage 8 4.3 Construction 9 4.4 Tests. 9 4.5 Guide to use (informative) 9 5 Heavy polychlo

15、roprene or other equivalent synthetic elastomer sheathed flexible cable. 13 5.1 Code designation. 12 5.2 Rated voltage 12 5.3 Construction 12 5.4 Tests. 13 5.5 Guide to use (informative) 13 6 Heavy polychloroprene or other equivalent synthetic elastomer sheathed flexible cable with more than five co

16、nductors (Multicore cables). 18 6.1 Code designation. 18 6.2 Rated Voltage 18 6.3 Construction 18 6.4 Tests. 20 6.5 Guide to use (informative) 20 Annex A (normative) Special national conditions (normative).23 Bibliography.24 HD 22.4 S4:2004 - 4 - 1 Scope This Part 4 of the HD details the particular

17、specifications for EPR insulated and EPR or polychloroprene or other equivalent synthetic elastomer sheathed cords and flexible cables of rated voltages up to and including 450/750 V. All cables shall comply with the appropriate requirements given in Part 1 of this HD and the individual types of cab

18、le shall each comply with the particular requirements of this part. NOTE The overall dimensions of the cables in this part of HD 22 have been calculated in accordance with EN 60719. 2 Normative references The following referenced documents are indispensable for the application of this document. For

19、dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. Publication Year Title EN 50265-2-1 1998 Common test methods for cables under fire conditions - Test for resistance to vertical flame propagatio

20、n for a single insulated conductor or cable Part 2-1 : Procedures - 1kW pre-mixed flame EN 50334 2001 Marking by inscription for the identification of cores of electric cables EN 50356 2002 Method of spark testing of cables EN 60811 (series) Insulating and sheathing materials of electric and optical

21、 cables - Common test methods HD 383 1993 Conductors of insulated cables (Endorsing IEC 60228 and IEC 60228A) Table 1 (Spare) Table 2 (Spare) 3 Ordinary EPR insulated and EPR sheathed cord and flexible cable 1) 3.1 Code designation H05RR-F 3.2 Rated voltage 300/500 V 1) This is similar to type 60245

22、 IEC 57 up to 1,0 mm but has modified requirements. -,-,- - 5 - HD 22.4 S4:2004 3.3 Construction 3.3.1 Conductor Number of conductors: 2, 3, 4 or 5. Cross sectional areas: 0,75 mm up to and including 4 mm for cables having 2 to 5 conductors; 6 mm for cables having 3 or 4 conductors. The conductors s

23、hall be in accordance with the requirements given in HD 383 for Class 5 conductors. The wires may be plain or tinned. 3.3.2 Separator A separator of suitable material may be applied around each conductor. 3.3.3 Insulation The insulation shall be rubber compound of Type EI 4 applied around each condu

24、ctor. The insulation shall be applied by extrusion. The insulation thickness shall comply with the specified value given in Part 4, Table 3, column 2. 3.3.4 Assembly of cores and filler, if any The cores shall be twisted together. A centre filler may be used. 3.3.5 Sheath The sheath shall be rubber

25、compound of Type EM 3, applied around the cores. The thickness of sheath shall comply with the specified value given in Part 4, Table 3, column 3. The sheath shall be extruded and applied in such a way that it fills the spaces between the cores. The sheath shall be capable of being removed without d

26、amage to the cores. The colour of sheath is not specified, but if black is used it shall be subject to the test for carbon black content given in Part 4, Table 4, with a requirement for a minimum level as given for EM 3 in Part 1, Table 2. 3.3.6 Overall diameter The mean overall diameter shall be wi

27、thin the limits given in Part 4 Table 3, columns 4 and 5. 3.3.7 Outer marking The cable shall have the marking H05RR-F printed or embossed on, or indented into, the outer surface of the sheath, or on the insulation of one of the cores. The marking, which shall meet the requirements of 3.2 and 3.3 of

28、 Part 1, shall be legible. 3.4 Tests Compliance with the requirements of Part 4, Subclause 3.3 shall be checked by inspection and by the tests given in Part 4, Table 4. 3.5 Guide to use (informative) See HD 516. -,-,- HD 22.4 S4:2004 - 6 - Table 3 Dimensions of type H05RR-F 1 2 3 4 5 Mean overall di

29、ameter Number and nominal cross- sectional area of conductors Thickness of insulation Specified value Thickness of sheath Specified value Lower limit Upper limit mm mm mm mm mm 2 x 0,75 0,6 0,8 5,7 7,4 2 x 1 0,6 0,9 6,1 8,0 2 x 1,5 0,8 1,0 7,6 9,8 2 x 2,5 0,9 1,1 9,0 11,6 2 x 4 1,0 1,2 10,6 13,7 3 x

30、 0,75 0,6 0,9 6,2 8,1 3 x 1 0,6 0,9 6,5 8,5 3 x 1,5 0,8 1,0 8,0 10,4 3 x 2,5 0,9 1,1 9,6 12,4 3 x 4 1,0 1,2 11,3 14,5 3 x 6 1,0 1,4 12,8 16,3 4 x 0,75 0,6 0,9 6,8 8,8 4 x 1 0,6 0,9 7,1 9,3 4 x 1,5 0,8 1,1 9,0 11,6 4 x 2,5 0,9 1,2 10,7 13,8 4 x 4 1,0 1,3 12,7 16,2 4 x 6 1,0 1,5 14,2 18,1 5 x 0,75 0,6

31、 1,0 7,6 9,9 5 x 1 0,6 1,0 8,0 10,3 5 x 1,5 0,8 1,1 9,8 12,7 5 x 2,5 0,9 1,3 11,9 15,3 5 x 4 1,0 1,4 14,6 18,6 - 7 - HD 22.4 S4:2004 Table 4 Tests for type H05RR-F 1 2 3 4 5 Ref. No. Tests Cate- gory of test Test method described in HD / EN Clause 1. Electrical tests 1.1 Resistance of conductors T,

32、S 22.2 2.1 1.2 Voltage test on cores according to specified insulation thickness 1.2.1 at 1 500 V up to and including 0,6 mm T 22.2 2.3 1.2.2 at 2 000 V exceeding 0,6 mm T 22.2 2.3 1.3 Voltage test on completed cable at 2 000 V T, S 22.2 2.2 1.4 Absence of faults on insulation R 22.2 a 2.6 1.5 Surfa

33、ce resistance of sheath T 22.2 2.7 2 Provisions covering constructional and dimensional characteristics 2.1 Checking of compliance with constructional provisions T, S 22.1 Inspection and manual tests 2.2 Measurement of thickness of insulation T, S 22.2 1.9 2.3 Measurement of thickness of sheath T, S

34、 22.2 1.10 2.4 Measurement of overall diameter 2.4.1 Mean value T, S 22.2 1.11 2.4.2 Ovality T, S 22.2 1.11 2.5 Solderability test (Plain conductors) T 22.2 1.12 3 Mechanical properties of insulation 3.1 Tensile test before ageing T 60811-1-1 9.1 3.2 Tensile test after ageing in the air oven T 60811

35、-1-2 8.1.3.2a 3.3 Tensile test after ageing in the air bomb T 60811-1-2 8.2 3.4 Hot set test T 60811-2-1 9 4 Mechanical properties of sheath 4.1 Tensile test before ageing T 60811-1-1 9.2 4.2 Tensile test after ageing in the air oven T 60811-1-2 8.1.3.1 4.3 Hot set test T 60811-2-1 9 5 Compatibility

36、 test on cable T 60811-1-2 8.1.4 HD 22.4 S4:2004 - 8 - Table 4 Tests for type H05RR-F (continued) 1 2 3 4 5 Ref. No. Tests Cate- gory of test Test method described in HD / EN Clause 6 Mechanical strength of completed cable 6.1 Flexing test b followed, after immersion in water, by a voltage test on c

37、ores - at 1 500 V on cores with specified insulation thickness up to and including 0,6 mm T 22.2 3.1 and 2.3 - at 2 000 V on cores with specified insulation thickness exceeding 0,6 mm T 22.2 3.1 and 2.3 7 Tests at low temperature 7.1 Bending test on sheath c T 60811-1-4 8.2 7.2 Elongation test on sh

38、eath d T 60811-1-4 8.4 7.3 Impact test on cable at 25 C T 60811-1-4 8.5 8 Carbon black content of sheath (where applicable) T 60811-4-1 11 9 Ozone resistance test for insulation and sheath (either method may be used) T (a) Method A 60811-2-1 8 (b) Method B 22.2 7.3 a Where the spark test is used for

39、 checking absence of faults on insulation, EN 50356 may be used in place of the method in HD 22.2. b Not applicable to cables with conductors greater than 4 mm c Only applicable to cables having mean overall diameters up to and including 12,5 mm d Only applicable if the mean overall diameter of the

40、cable exceeds 12,5 mm 4 Ordinary polychloroprene or other equivalent synthetic elastomer sheathed cord and flexible cable 2) 4.1 Code designation H05RN-F 4.2 Rated voltage 300/500 V 2) This is similar to type 60245 IEC 57 up to 1,0 mm but has modified requirements. - 9 - HD 22.4 S4:2004 4.3 Construc

41、tion 4.3.1 Conductor Number of conductors: 2 or 3. The conductors shall comply with the requirements given in HD 383 for Class 5 conductors. The wires may be plain or tinned. 4.3.2 Separator A separator of suitable material may be applied around each conductor. 4.3.3 Insulation The insulation shall

42、be rubber compound of Type EI 4 applied around each conductor. The insulation shall be applied by extrusion. The insulation thickness shall comply with the specified value given in Part 4, Table 5, column 2. 4.3.4 Assembly of cores and filler, if any The cores shall be twisted together. A centre fil

43、ler may be used. 4.3.5 Sheath The sheath shall be rubber compound of Type EM 2 applied around the cores. The thickness of sheath shall comply with the specified value given in Part 4, Table 5, column 3. The sheath shall be extruded in a single layer and applied in such a way that it fills the spaces

44、 between the cores. The sheath shall be capable of being removed without damage to the cores. 4.3.6 Overall diameter The mean overall diameter shall be within the limits given in Part 4, Table 5, columns 4 and 5. 4.3.7 Outer marking The cable shall have the marking H05RN-F printed or embossed on, or

45、 indented into, the outer surface of the polychloroprene sheath. The marking, which shall meet the requirements of 3.2 and 3.3 of Part 1, shall be legible. 4.4 Tests Compliance with the requirements of Part 4, Subclause 4.3 shall be checked and inspected by the tests given in Part 4, Table 6. 4.5 Gu

46、ide to use (informative) See HD 516. -,-,- HD 22.4 S4:2004 - 10 - Table 5 Dimensions of type H05RN-F 1 2 3 4 5 Number and nominal cross- sectional area of conductors Thickness of insulation Specified value Thickness of sheath Specified value Mean overall diameter Lower limit Upper limit mm mm mm mm

47、mm 2 x 0,75 0,6 0,8 5,7 7,4 2 x 1 0,6 0,9 6,1 8,0 3 x 0,75 0,6 0,9 6,2 8,1 3 x 1 0,6 0.9 6.5 8.5 Table 6 - Tests for Type H05RN-F 1 2 3 4 5 Ref. No. Tests Cate- gory of test Test method described in HD / EN Clause 1 Electrical tests 1.1 Resistance of conductors T, S 22.2 2.1 1.2 Voltage test on core

48、s at 1 500 V T 22.2 2.3 1.3 Voltage test on completed cable at 2 000 V T, S 22.2 2.2 1.4 Absence of faults on insulation R 22.2 a 2.6 1.5 Surface resistance of sheath T 22.2 2.7 2 Provisions covering constructional and dimensional characteristics 2.1 Checking of compliance with constructional provis

49、ions T, S 22.1 Inspection and manual tests 2.2 Measurement of thickness of insulation T, S 22.2 1.9 2.3 Measurement of thickness of sheath T, S 22.2 1.10 2.4 Measurement of overall diameter 2.4.1 Mean value T, S 22.2 1.11 2.4.2 Ovality T, S 22.2 1.11 2.5 Solderability test (Plain conductors) T 22.2 1.12 -,-,- - 11 - HD 22.4 S4:200