BS EN 13999-3-2009 Adhesives — Short term method for measuring the emission properties of low-solvent or solvent-free adhesives after application — Part 3 Determination of volatile aldehydes.pdf

上传人:韩长文 文档编号:3644339 上传时间:2019-09-19 格式:PDF 页数:14 大小:144.46KB
返回 下载 相关 举报
BS EN 13999-3-2009 Adhesives — Short term method for measuring the emission properties of low-solvent or solvent-free adhesives after application — Part 3 Determination of volatile aldehydes.pdf_第1页
第1页 / 共14页
BS EN 13999-3-2009 Adhesives — Short term method for measuring the emission properties of low-solvent or solvent-free adhesives after application — Part 3 Determination of volatile aldehydes.pdf_第2页
第2页 / 共14页
BS EN 13999-3-2009 Adhesives — Short term method for measuring the emission properties of low-solvent or solvent-free adhesives after application — Part 3 Determination of volatile aldehydes.pdf_第3页
第3页 / 共14页
BS EN 13999-3-2009 Adhesives — Short term method for measuring the emission properties of low-solvent or solvent-free adhesives after application — Part 3 Determination of volatile aldehydes.pdf_第4页
第4页 / 共14页
BS EN 13999-3-2009 Adhesives — Short term method for measuring the emission properties of low-solvent or solvent-free adhesives after application — Part 3 Determination of volatile aldehydes.pdf_第5页
第5页 / 共14页
亲,该文档总共14页,到这儿已超出免费预览范围,如果喜欢就下载吧!
资源描述

《BS EN 13999-3-2009 Adhesives — Short term method for measuring the emission properties of low-solvent or solvent-free adhesives after application — Part 3 Determination of volatile aldehydes.pdf》由会员分享,可在线阅读,更多相关《BS EN 13999-3-2009 Adhesives — Short term method for measuring the emission properties of low-solvent or solvent-free adhesives after application — Part 3 Determination of volatile aldehydes.pdf(14页珍藏版)》请在三一文库上搜索。

1、BRITISH STANDARD Adhesives Short term method for measuring the emission properties of low-solvent or solvent-free adhesives after application Part 3: Determination of volatile aldehydes ICS 83.180 ? BS EN 13999-3:2007 +A1:2009 This British Standard was published under the authority of the Standards

2、Policy and Strategy Committee on 31 May 2007 BSI 2009 ISBN 978 0 580 63986 9 National foreword BS EN 13999-3:2007+A1:2009 This British Standard is the UK implementation of EN 13999-3:2007+A1:2009. It supersedes BS EN 13999-3:2007 which is The start and finish of text introduced or altered by amendme

3、nt is indicated in the text by tags. Tags indicating changes to CEN text carry the number of CEN amendment. For example, text altered by CEN amendment A1 is indicated by ab. The UK participation in its preparation was entrusted to Technical Committee PRI/52, Adhesives. A list of organizations repres

4、ented on this committee can be obtained on request to its secretary. This publication does not purport to include all the necessary provisions of a contract. Users are responsible for its correct application. Compliance with a British Standard cannot confer immunity from legal obligations. withdrawn

5、. DateComments June 2009 Implementation of CEN amendment A1:2009 Amendments/corrigenda issued since publication the 30 EUROPEAN STANDARD NORME EUROPENNE EUROPISCHE NORM EN 13999-3:2007+A1 April 2009 ICS 83.180Supersedes EN 13999-3:2007 English Version Adhesives - Short term method for measuring the

6、emission properties of low-solvent or solvent-free adhesives after application - Part 3: Determination of volatile aldehydes Adhsifs - Mthodes de mesurage rapide des caractristiques missives des adhsifs teneur faible ou nulle en solvants aprs application - Partie 3: Dosage des aldhydes volatiles Kle

7、bstoffe - Kurzzeit-Verfahren zum Messen der Emissionseigenschaften von lsemittelarmen oder lsemittelfreien Klebstoffen nach der Applikation - Teil 3: Bestimmung flchtiger Aldehyde This European Standard was approved by CEN on 8 March 2007 and includes Amendment 1 approved by CEN on 3 April 2009. CEN

8、 members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on appl

9、ication to the CEN Management Centre or to any CEN member. This European Standard exists in three official versions (English, French, German). A version in any other language made by translation under the respons bility of a CEN member into its own language and notified to the CEN Management Centre

10、has the same status as the official versions. CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland,

11、Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom. EUROPEAN COMMITTEE FOR STANDARDIZATION COMIT EUROPEN DE NORMALISATION EUROPISCHES KOMITEE FR NORMUNG Management Centre: Avenue Marnix 17, B-1000 Brussels 2009 CEN All rights of exploitation in any form and by any m

12、eans reserved worldwide for CEN national Members. Ref. No. EN 13999-3:2007+A1:2009: E EN 13999-3:2007+A1:2009 (E) 2 Contents Page Foreword 3 SAFETY STATEMENT .4 1Scope 4 2Normative references 4 3Principle 4 4Reagents .5 5Apparatus .5 6Procedure .5 7Identification and calculation .7 8Interferences 8

13、9Precision and bias .8 10Test report 8 11Quality control 9 Bibliography . 10 BS EN 13999-3:2007+A1:2009 EN 13999-3:2007+A1:2009 (E) 3 Foreword This document (EN 13999-3:2007+A1:2009) has been prepared by Technical Committee CEN/TC 193 “Adhesives”, the secretariat of which is held by AENOR. This Euro

14、pean Standard shall be given the status of a national standard, either by publication of an identical text or by endorsement, at the latest by October 2009, and conflicting national standards shall be withdrawn at the latest by October 2009. This document includes Amendment 1, approved by CEN on 200

15、9-04-03. This document supersedes !EN 13999-3:2007“. The start and finish of text introduced or altered by amendment is indicated in the text by tags ! “. According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following countries are bound to implement this Eu

16、ropean Standard: Austria, Belgium, Bulgaria, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United K

17、ingdom. BS EN 13999-3:2007+A1:2009 ? ation on Bulgaria, Bulgaria, Iceland, Ire celand, Ire www.bzfxw.co Romania, Slo mania, Slo EN 13999-3:2007+A1:2009 (E) 4 SAFETY STATEMENT Persons using this European Standard should be familiar with the normal laboratory practice, if applicable. This Europea

18、n Standard does not purport to address all of the safety problems, if any, associated with its use. It is the responsibility of the user to establish appropriate health and safety practices and to ensure compliance with any regulatory conditions. 1 Scope This European Standard specifies a procedure

19、for the determination of volatile aldehydes (especially formaldehyde and acetaldehyde) and other carbonyl compounds in the exhaust air of an emission test chamber after application of a low-solvent or solvent-free adhesive as defined in EN 923. The method is based on chemosorption of volatile carbon

20、yl compounds with 2,4-dinitrophenylhydrazine (in the following: DNPH) impregnated silica tubes or cartridges with subsequent solvent desorption, clean-up and liquid chromatographic analysis. The method permits measurement of several aldehydes including formaldehyde, acetaldehyde, propionaldehyde, bu

21、tyraldehyde, valeraldehyde, isovaleraldehyde, hexanal, benzaldehyde, 2,5-dimethylbenzaldehyde, o-tolualdehyde, m-tolualdehyde, p-tolualdehyde, crotonaldehyde in the concentration range of approximately 10 g/m to 1 mg/m (see ISO 16000-3). 2 Normative references The following referenced documents are

22、indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. EN 1232, Workplace atmospheres Pumps for personal sampling of chemical agents Requiremen

23、ts and test methods EN 13999-1, Adhesives Short term method for measuring the emission properties of low-solvent or solvent- free adhesives after application Part 1: General procedure EN ISO 16000-9, Indoor air Part 9: Determination of the emission of volatile organic compounds from building product

24、s and furnishing Emission test chamber method (ISO 16000-9:2006) ISO 16000-3, Indoor air Part 3: Determination of formaldehyde and other carbonyl compounds Active sampling method 3 Principle A sufficient volume of test chamber air is drawn with an appropriate flow through silicagel tubes or cartridg

25、es impregnated with 2,4-dinitrophenylhydrazine (DNPH) reagent. Any organic aldehydes and other carbonyl compounds present will react to form non-volatile dinitrophenylhydrazones. Desorption is done with acetonitrile. The resultant solution is concentrated and analysed by high performance liquid chro

26、matography (HPLC) with ultraviolet (UV) detection. Dinitrophenylhydrazone peaks from formaldehyde, acetaldehyde and other aldehydes are identified on the basis of both their respective retention times and their UV responses at more than one wavelength and/or by diode array detection (DAD) and compar

27、ison with a derivative product (where available) or standard. Quantification is done by comparison with a relevant aldehyde or a dinitrophenylhydrazone standard. BS EN 13999-3:2007+A1:2009 ? Pumps ? Pumps ? es Short term ? s Short t fter application ? er application Indo ? Indo des ldehyde, hyde,

28、 hyde, crotona de, crotona le for the ap for the ap ndated refere ated refere r p r p EN 13999-3:2007+A1:2009 (E) 5 4 Reagents 4.1 Acetonitrile Acetonitrile of HPLC grade. 4.2 Standards Commercially available DNPH-aldehyde derivatives (or their solution(s) in acetonitrile). If the DNPH-aldehyde

29、derivatives are prepared in the laboratory, the respective reagents described in ISO 16000-3 shall be used. 5 Apparatus 5.1 Sampler Commercially available tubes or cartridges filled with DNPH coated silica. If the samplers are prepared in the laboratory the respective reagents described in ISO 16000

30、-3 shall be used. The ratio of the silica gel bed diameter to bed length shall not exceed 1:1. The capacity of the tube or cartridge for formaldehyde shall be at least 75 g and adsorption efficiency at least 95 % at the sampling rate applied. 5.2 Sampling pump The pump shall fulfil the requirements

31、of EN 1232 or equivalent. 5.3 Tubing Tubing of appropriate diameter to ensure a leak-proof fit to both pump and sample tube. PTFE tubes shall be used upstream of the sorbent to avoid loss of substance due to reaction with tubing walls. 5.4 Flow meter calibrator Bubble meter or other appropriate suit

32、able device for gas flow calibration. 5.5 High performance liquid chromatograph (HPLC) A typical apparatus for HPLC, with ultraviolet (UV) detector. 5.6 Emission test chamber An emission test chamber as described in EN 13999-1 or EN ISO 16000-9 shall be used. 6 Procedure 6.1 Test chamber air samplin

33、g Open the sealed tubes or remove the caps from the sampler and assemble the sampling line. Always use a sampler with a sampling section and a control section, or use two samplers in series with the downstream sampler serving as a control section. Prepare the test chamber sampling port as described

34、in EN 13999-1 or in EN ISO 16000-9. If the sampling flow rate is determined with a calibrator, start the pump, note and record the sampling flow rate. BS EN 13999-3:2007+A1:2009 ? rator ? ator r other appropria ? other appropri gh perform ? h perform mald a leak-proof fi eak-proof f oss of substa

35、 s of subs EN 13999-3:2007+A1:2009 (E) 6 Connect the sampler to the chamber sampling port, note and record the time the sampler was connected. !Never use more than 90 % of the test chamber supply air flow“ rate as the combined sampling flow rates. At the end of the sampling period disconnect the sam

36、pler from the chamber sampling port, note and record the time of disconnection, repeat the sampling flow determination, turn off the pump. Disconnect the sampler or the samplers from the sampling line and seal both ends using inert caps. NOTE The recommended sampling flow rate is in the range of 0,2

37、 l/min. The recommended air volume is 24 l. 6.2 Storage of loaded samplers Store each sampler so that it is isolated from other samples and from sources for volatile aldehydes, protected from light. If not analysed on the same day that the sample is collected, store the samplers at a temperature bel

38、ow 10 C. The time between sampling and analysis shall be as short as possible and shall not exceed 14 days. 6.3 Blanks Take at least one blank sample which is a sampler equivalent to the ones used for sampling. Subject the blank samples to the same handling procedure in the laboratory as the actual

39、samples except for the actual period of sampling, i.e. repeat the sampling procedure up to the point of actual sample collection. Do not perform sampling but repeat normal post-sampling procedure for the sampling tubes. Mark, store and analyse blank samples in sequence with the actual samples. For b

40、lank control of the test chamber see EN 13999-1. 6.4 Analysis 6.4.1 Cleaning of glassware Before use, clean all glassware to remove any residual grease or chemicals by soaking overnight in laboratory detergent solution and then rinsing thoroughly with water. Alternatively, use a laboratory washing m

41、achine. 6.4.2 Sample desorption (cartridges) Desorb samples, blanks and standards by slowly passing a small amount of acetonitrile through the cartridges as described in ISO 16000-3. 6.4.3 Sample desorption (tubes) Desorb samples, blanks and standards by separately emptying the content of the sectio

42、ns of the tube, adding a small amount of acetonitrile as described in ISO 16000-3 and letting it stand at room temperature in the dark for at least 30 min with occasional agitation. 6.4.4 Standard solutions Prepare standard solutions in the analytical range of interest from commercially available DN

43、PH-aldehyde derivatives (or their solution(s) in acetonitrile), or from self-produced DNPH-aldehyde derivatives as described in ISO 16000-3. Store all standard solutions in tightly capped containers in a refrigerator and keep protected from light. Allow them to equilibrate to room temperature before

44、 use. They should be replaced after four weeks. 6.4.5 Calibration of liquid chromatograph Calibrate the system by injecting a known fixed volume (e.g. 25 l) of at least five standard solutions covering the analytical range of interest into the liquid chromatograph using UV detection as described bel

45、ow. A standardised injection technique is required to obtain reproducible peak heights/areas. Prepare a calibration graph of UV response versus analyte concentration in the standard solutions as described in ISO 16000-3. BS EN 13999-3:2007+A1:2009 ? ridges) ? dges) ? and standards ? and standards 16

46、000-3. ? 6000-3. sorpt ? sorp for collection lection Mark, store an rk, store an hamber see E er see E dual grease o al grease o with water. A th water. A EN 13999-3:2007+A1:2009 (E) 7 Once linear response (correlation coefficient of at least 0,999 for response versus concentration) has been

47、documented, an intermediate concentration standard near the anticipated levels of component, but at least ten times the detection limit, should be chosen for daily calibration. The day to day response of the analytical system for the various components shall be registered on a control card or in a c

48、orresponding electronic data system and should be within 20 %. If greater variability is observed the system shall be checked, re-calibrated and fresh standards shall be prepared. 6.4.6 Analysis of desorbed sample solutions Inject a known fixed volume (25 l) of the desorbed sample solution into the liquid chromatograph. Determine the UV response at the retention times being specific for the respective DNPH-aldehyde derivatives

展开阅读全文