BS EN 14511-1-2007 Air conditioners, liquid chilling packages and heat pumps with electrically driven compressors for space heating and cooling.pdf

上传人:韩长文 文档编号:3646901 上传时间:2019-09-19 格式:PDF 页数:16 大小:343.23KB
返回 下载 相关 举报
BS EN 14511-1-2007 Air conditioners, liquid chilling packages and heat pumps with electrically driven compressors for space heating and cooling.pdf_第1页
第1页 / 共16页
BS EN 14511-1-2007 Air conditioners, liquid chilling packages and heat pumps with electrically driven compressors for space heating and cooling.pdf_第2页
第2页 / 共16页
BS EN 14511-1-2007 Air conditioners, liquid chilling packages and heat pumps with electrically driven compressors for space heating and cooling.pdf_第3页
第3页 / 共16页
BS EN 14511-1-2007 Air conditioners, liquid chilling packages and heat pumps with electrically driven compressors for space heating and cooling.pdf_第4页
第4页 / 共16页
BS EN 14511-1-2007 Air conditioners, liquid chilling packages and heat pumps with electrically driven compressors for space heating and cooling.pdf_第5页
第5页 / 共16页
亲,该文档总共16页,到这儿已超出免费预览范围,如果喜欢就下载吧!
资源描述

《BS EN 14511-1-2007 Air conditioners, liquid chilling packages and heat pumps with electrically driven compressors for space heating and cooling.pdf》由会员分享,可在线阅读,更多相关《BS EN 14511-1-2007 Air conditioners, liquid chilling packages and heat pumps with electrically driven compressors for space heating and cooling.pdf(16页珍藏版)》请在三一文库上搜索。

1、BRITISH STANDARD BS EN 14511-1:2007 Air conditioners, liquid chilling packages and heat pumps with electrically driven compressors for space heating and cooling Part 1: Terms and definitions The European Standard EN 14511-1:2007 has the status of a British Standard ICS 01.040.23; 23.120 ? Licensed c

2、opy:PONTYPRIDD COLLEGE, 12/01/2008, Uncontrolled Copy, BSI BS EN 14511-1:2007 This British Standard was published under the authority of the Standards Policy and Strategy Committee on 31 December 2007 BSI 2007 ISBN 978 0 580 58327 8 National foreword This British Standard is the UK implementation of

3、 EN 14511-1:2007. It supersedes BS EN 14511-1:2004 which is withdrawn. The UK participation in its preparation was entrusted to Technical Committee RHE/17, Testing of air conditioning units. A list of organizations represented on this committee can be obtained on request to its secretary. This publi

4、cation does not purport to include all the necessary provisions of a contract. Users are responsible for its correct application. Compliance with a British Standard cannot confer immunity from legal obligations. Amendments issued since publication Amd. No. DateComments Licensed copy:PONTYPRIDD COLLE

5、GE, 12/01/2008, Uncontrolled Copy, BSI 标准分享网 w w w .b z f x w .c o m 免费下载 EUROPEAN STANDARD NORME EUROPENNE EUROPISCHE NORM EN 14511-1 November 2007 ICS 23.120; 01.040.23Supersedes EN 14511-1:2004 English Version Air conditioners, liquid chilling packages and heat pumps with electrically driven comp

6、ressors for space heating and cooling - Part 1: Terms and definitions Climatiseurs, groupes refroidisseurs de liquide et pompes chaleur avec compresseur entran par moteur lectrique pour le chauffage et la rfrigration des locaux - Partie 1: Termes et dfinitions Luftkonditionierer, Flssigkeitskhlstze

7、und Wrmepumpen mit elektrisch angetriebenen Verdichtern fr die Raumbeheizung und Khlung - Teil 1: Begriffe This European Standard was approved by CEN on 13 October 2007. CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European

8、Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN Management Centre or to any CEN member. This European Standard exists in three official versions (English, F

9、rench, German). A version in any other language made by translation under the responsibility of a CEN member into its own language and notified to the CEN Management Centre has the same status as the official versions. CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Cypr

10、us, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom. EUROPEAN COMMITTEE FOR STANDARDIZATION CO

11、MIT EUROPEN DE NORMALISATION EUROPISCHES KOMITEE FR NORMUNG Management Centre: rue de Stassart, 36 B-1050 Brussels 2007 CENAll rights of exploitation in any form and by any means reserved worldwide for CEN national Members. Ref. No. EN 14511-1:2007: E Licensed copy:PONTYPRIDD COLLEGE, 12/01/2008, Un

12、controlled Copy, BSI EN 14511-1:2007 (E) 2 Contents Page Foreword3 1 Scope 4 2 Terms and definitions .4 3 Classification9 Index.11 Bibliography13 Licensed copy:PONTYPRIDD COLLEGE, 12/01/2008, Uncontrolled Copy, BSI 标准分享网 w w w .b z f x w .c o m 免费下载 EN 14511-1:2007 (E) 3 Foreword This document (EN 1

13、4511-1:2007) has been prepared by Technical Committee CEN/TC 113 “Heat pumps and air conditioning units”, the secretariat of which is held by AENOR. This European Standard shall be given the status of a national standard, either by publication of an identical text or by endorsement, at the latest by

14、 May 2008, and conflicting national standards shall be withdrawn at the latest by May 2008. Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights. CEN shall not be held responsible for identifying any or all such patent rights. This docu

15、ment supersedes EN 14511-1:2004. The revised standard takes into account double duct units and multisplit systems. EN 14511 comprises the following parts under the general title “Air conditioners, liquid chilling packages and heat pumps with electrically driven compressors for space heating and cool

16、ing“: - Part 1: Terms and definitions - Part 2: Test conditions - Part 3: Test methods - Part 4: Requirements According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria,

17、Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and the United Kingdom. Licensed copy:PONTYPRIDD COLLEGE,

18、 12/01/2008, Uncontrolled Copy, BSI EN 14511-1:2007 (E) 4 1 Scope This part of EN 14511 specifies the terms and definitions for the rating and performance of air and water cooled air conditioners, liquid chilling packages, air-to-air, water-to-air, air-to-water and water-to-water heat pumps with ele

19、ctrically driven compressors when used for space heating and/or cooling. This European Standard does not specifically apply to heat pumps for sanitary hot water, although certain definitions can be applied to these. This European Standard applies to factory-made units that can be ducted. This standa

20、rd applies to factory-made liquid chilling packages with integral condensers or for use with remote condensers. This standard applies to factory-made units of either fixed capacity or variable capacity by any means. Packaged units, single split and multisplit systems are covered by this standard. Si

21、ngle duct and double duct units are covered by the standard. In the case of units consisting of several parts, this standard applies only to those designed and supplied as a complete package, except for liquid chilling packages with remote condenser. This standard is primarily intended for water and

22、 brine chilling packages but can be used for other liquid subject to agreement. This standard applies to air-to-air air conditioners which evaporate the condensate on the condenser side. The units having their condenser cooled by air and by the evaporation of external additional water are not covere

23、d by this standard. This standard does not apply to units using transcritical cycles, e.g. with CO2 as refrigerant. Installations used for heating and/or cooling of industrial processes are not within the scope of this standard. NOTE 1 Part load testing of units is dealt with in CEN/TS 14825. NOTE 2

24、 All the symbols given in this text should be used regardless of the language used. 2 Terms and definitions For the purposes of this document, the following terms and definitions apply. 2.1 air conditioner encased assembly or assemblies designed as a unit to provide delivery of conditioned air to an

25、 enclosed space (room for instance) or zone. It includes an electrically operated refrigeration system for cooling and possibly dehumidifying the air. It can have means for heating, circulating, cleaning and humidifying the air. If the unit provides heating by reversing the refrigerating cycle then

26、it is a heat pump 2.2 heat pump encased assembly or assemblies designed as a unit to provide delivery of heat. It includes an electrically operated refrigeration system for heating. It can have means for cooling, circulating, cleaning and dehumidifying the air. The cooling is by means of reversing t

27、he refrigerating cycle Licensed copy:PONTYPRIDD COLLEGE, 12/01/2008, Uncontrolled Copy, BSI 标准分享网 w w w .b z f x w .c o m 免费下载 EN 14511-1:2007 (E) 5 2.3 comfort air conditioner or heat pump air conditioner or heat pump to satisfy the requirements of the occupants of the air conditioned room 2.4 clos

28、e control air conditioner air conditioner to satisfy the requirements of the process carried out in the air conditioned room 2.5 control cabinet air conditioner air conditioner to satisfy the requirements of the control cabinet 2.6 packaged unit factory assembly of components of refrigeration system

29、 fixed on a common mounting to form a discrete unit 2.7 single split unit factory assembly of components of refrigeration system fixed on two mountings or more to form a discrete matched functional unit 2.8 single-duct air conditioner air conditioner for spot cooling in which the condenser intake ai

30、r is introduced from the space containing the unit and discharged outside this space 2.9 double-duct air conditioner air conditioner placed in the conditioned space near a wall, in which the condenser intake air is introduced from the outdoor environment by a small duct and the condenser discharge a

31、ir is rejected to the outdoor environment by a second small duct 2.10 liquid chilling package factory-made unit designed to cool liquid, using an evaporator, a refrigerant compressor, an integral or remote condenser and appropriate controls. It may have means for heating which can be reversing the r

32、efrigerating cycle, like a heat pump 2.11 heat recovery liquid chilling package factory-made liquid chilling package designed for the purpose of chilling liquid and recovering of heat 2.12 heat recovery recovery of heat rejected by the unit(s) whose primary control is in the cooling mode by means of

33、 either an additional heat exchanger (e.g. a liquid chiller with an additional condenser) or by transferring the heat through the refrigerating system for use to unit(s) whose primary control remains in the heating mode (e.g. variable refrigerant flow) 2.13 indoor heat exchanger heat exchanger which

34、 is designed to transfer heat to the indoor part of the building or to the indoor hot water supplies or to remove heat from these NOTE In the case of an air conditioner or heat pump operating in the cooling mode, this is the evaporator. In the case of an air conditioner or heat pump operating in the

35、 heating mode, this is the condenser. Licensed copy:PONTYPRIDD COLLEGE, 12/01/2008, Uncontrolled Copy, BSI EN 14511-1:2007 (E) 6 2.14 outdoor heat exchanger heat exchanger which is designed to remove heat from the outdoor ambient environment, or any other available heat source, or to transfer heat t

36、o it NOTE In the case of an air conditioner or heat pump operating in the cooling mode, this is the condenser. In the case of an air conditioner heat pump operating in the heating mode, this is the evaporator. 2.15 heat recovery heat exchanger heat exchanger assembly which is designed to transfer he

37、at to the heat recovery medium 2.16 heat transfer medium any medium (water, air, .) used for the transfer of the heat without change of state EXAMPLES cooled liquid circulating in the evaporator; cooling medium circulating in the condenser; heat recovery medium circulating in the heat recovery heat

38、exchanger. 2.17 outside air air from the outdoor environment entering the outdoor heat exchanger 2.18 exhaust air air from the air conditioned space entering the outdoor heat exchanger 2.19 recycled air air from the air conditioned space entering the indoor heat exchanger 2.20 outdoor air air from t

39、he outdoor environment entering the indoor heat exchanger 2.21 water loop closed circuit of water maintained within a temperature range on which the units in cooling mode reject heat and the units in heating mode take heat 2.22 total cooling capacity PC heat given off from the heat transfer medium t

40、o the unit per unit of time, expressed in Watt 2.23 latent cooling capacity PL capacity of the unit for removing latent heat from the evaporator intake air, expressed in Watt 2.24 sensible cooling capacity PS capacity of the unit for removing sensible heat from the evaporator intake air, expressed i

41、n Watt 2.25 heating capacity PH heat given off by the unit to the heat transfer medium per unit of time, expressed in Watt Licensed copy:PONTYPRIDD COLLEGE, 12/01/2008, Uncontrolled Copy, BSI 标准分享网 w w w .b z f x w .c o m 免费下载 EN 14511-1:2007 (E) 7 NOTE If heat is removed from the indoor heat exchan

42、ger for defrosting, it is taken into account. 2.26 heat rejection capacity heat removed by the heat transfer medium of the condenser per unit of time, expressed in Watt NOTE This applies only to heat recovery liquid chilling packages. 2.27 heat recovery capacity heat removed by the heat transfer med

43、ium of the heat recovery heat exchanger, per unit of time, expressed in Watt NOTE This applies only to heat recovery liquid chilling packages. 2.28 total power input PT power input of all components of the unit as delivered, expressed in Watt 2.29 effective power input PE average electrical power in

44、put of the unit within the defined interval of time obtained from: power input for operation of the compressor and any power input for defrosting; power input for all control and safety devices of the unit; and proportional power input of the conveying devices (e.g. fans, pumps) for ensuring the tra

45、nsport of the heat transfer media inside the unit. It is expressed in Watt 2.30 energy efficiency ratio EER ratio of the total cooling capacity to the effective power input of the unit, expressed in Watt/Watt 2.31 sensible heat ratio SHR ratio of the sensible cooling capacity to the total cooling ca

46、pacity, expressed in Watt/Watt 2.32 coefficient of performance COP ratio of the heating capacity to the effective power input of the unit, expressed in Watt/Watt 2.33 operating range range indicated by the manufacturer and limited by the upper and lower limits of use (e.g. temperatures, air humidity

47、, voltage) within which the unit is deemed to be fit for use and has the characteristics published by the manufacturer 2.34 rating conditions standardised conditions provided for the determination of data which are characteristic for the unit, especially: Licensed copy:PONTYPRIDD COLLEGE, 12/01/2008

48、, Uncontrolled Copy, BSI EN 14511-1:2007 (E) 8 heating capacity, power input, COP in heating mode; cooling capacity, power input, EER, SHR in cooling mode. 2.35 defrost mode state of the unit in the heating mode where the operation is modified or reversed to defrost the outdoor heat exchanger 2.36 d

49、efrost period time for which the unit is in the defrost mode 2.37 operating cycle with defrost cycle consisting of a heating period and a defrost period, from defrost termination to defrost termination 2.38 temperature of saturated vapour at the discharge of the compressor temperature of saturated vapour/bubble point of the refrigerant corresponding to the discharge pressure of the compressor, measured at the compressor/piping connec