1、a Date: 20 January 2009 Origin: International Latest date for receipt of comments: 30 April 2009 Project no.: 2009/00700 Responsible committee: GEL/81 Protection against lightning Interested committees: Title: Draft BS EN 62561-4 ED1 Requirements for Lightning Protection System Components (LPSC) - P

2、art 4: Requirements for fasteners Supersession information: If this document is published as a standard, the UK implementation of it will supersede NONE and partially supersede. NONE If you are aware of a current national standard which may be affected, please notify the secretary (contact details b

3、elow). WARNING: THIS IS A DRAFT AND MUST NOT BE REGARDED OR USED AS A BRITISH STANDARD. THIS DRAFT IS NOT CURRENT BEYOND 30 April 2009. This draft is issued to allow comments from interested parties; all comments will be given consideration prior to publication. No acknowledgement will normally be s

4、ent. See overleaf for information on commenting. No copying is allowed, in any form, without prior written permission from BSI except as permitted under the Copyright, Designs and Patent Act 1988 or for circulation within a nominating organization for briefing purposes. Electronic circulation is lim

5、ited to dissemination by e-mail within such an organization by committee members. Further copies of this draft may be purchased from BSI Customer Services, Tel: +44(0) 20 8996 9001 or email . British, International and foreign standards are also available from BSI Customer Services. Information on t

6、he co-operating organizations represented on the committees referenced above may be obtained from the responsible committee secretary. Cross-references The British Standards which implement International or European publications referred to in this draft may be found via the British Standards Online

7、 Service on the BSI web site http:/. Direct tel: 020 8996 7288 Responsible Committee Secretary: Mr K Stiles (BSI) E-mail: Draft for Public Comment Head Office 389 Chiswick High Road London W4 4AL Telephone: +44(0)20 8996 9000 Fax: +44(0)20 8996 7001 Form 36 Version 8.0 DPC: 09/30197921 DC Licensed

8、Copy: London South Bank University, South Bank University, 02/02/2009 05:37, Uncontrolled Copy, (c) BSI b Introduction This draft standard is based on international discussions in which the UK has taken an active part. Your comments on this draft are welcome and will assist in the preparation of the

9、 consequent standard. There is a high probability that this text could be adopted by CENELEC as a reference document for harmonization or as a European Standard. Recipients of this draft are requested to comment on the text bearing in mind this possibility. UK Vote Please indicate whether you consid

10、er the UK should submit a negative (with reasons) or positive vote on this draft. Submission The guidance given below is intended to ensure that all comments receive efficient and appropriate attention by the responsible BSI committee. Annotated drafts are not acceptable and will be rejected. All co

11、mments must be submitted, preferably electronically, to the Responsible Committee Secretary at the address given on the front cover. Comments should be compatible with Version 6.0 or Version 97 of Microsoft Word for Windows, if possible; otherwise comments in ASCII text format are acceptable. Any co

12、mments not submitted electronically should still adhere to these format requirements. All comments submitted should be presented as given in the example below. Further information on submitting comments and how to obtain a blank electronic version of a comment form are available from the BSI web sit

13、e at: http:/ Template for comments and secretariat observations Date: xx/xx/200x Document: ISO/DIS xxxxx 1 2 (3) 4 5 (6) (7) MB Clause No./ Subclause No./ Annex (e.g. 3.1) Paragraph/ Figure/Table/ Note (e.g. Table 1) Type of com- ment Comment (justification for change) by the MB Proposed change by t

14、he MB Secretariat observations on each comment submitted 3.1 Definition 1 ed Definition is ambiguous and needs clarifying. Amend to read . so that the mains connector to which no connection . 6.4 Paragraph 2 te The use of the UV photometer as an alternative cannot be supported as serious problems ha

15、ve been encountered in its use in the UK. Delete reference to UV photometer. Microsoft and MS-DOS are registered trademarks, and Windows is a trademark of Microsoft Corporation. Licensed Copy: London South Bank University, South Bank University, 02/02/2009 05:37, Uncontrolled Copy, (c) BSI FORM CD (

16、IEC) 2009-01-09 Registered trademark of the International Electrotechnical Commission 81/313/CD COMMITTEE DRAFT (CD) IEC/TC or SC: TC 81 Project number IEC 62561-4 Ed.1.0 Title of TC/SC: Lightning Protection Date of circulation 2009-01-16 Closing date for comments 2009-04-17 Also of interest to the

17、following committees SC 37A,TC 64,TC 77 Supersedes document 81/306/NP 81/310/RVN Proposed horizontal standard Other TC/SCs are requested to indicate their interest, if any, in this CD to the TC/SC secretary Functions concerned: Safety EMC Environment Quality assurance Secretary: Mr. G.B. Lo Piparo e

18、-mail: lopiparorai.it THIS DOCUMENT IS STILL UNDER STUDY AND SUBJECT TO CHANGE. IT SHOULD NOT BE USED FOR REFERENCE PURPOSES. RECIPIENTS OF THIS DOCUMENT ARE INVITED TO SUBMIT, WITH THEIR COMMENTS, NOTIFICATION OF ANY RELEVANT PATENT RIGHTS OF WHICH THEY ARE AWARE AND TO PROVIDE SUPPORTING DOCUMENTA

19、TION. Title: IEC 62561-4 Ed. 1.0: Requirements for Lightning Protection System Components (LPSC) - Part 4: Requirements for fasteners (Titre) : Introductory note Copyright 2009 International Electrotechnical Commission, IEC. All rights reserved. It is permitted to download this electronic file, to m

20、ake a copy and to print out the content for the sole purpose of preparing National Committee positions. You may not copy or “mirror“ the file or printed version of the document, or any part of it, for any other purpose without permission in writing from IEC. Licensed Copy: London South Bank Universi

21、ty, South Bank University, 02/02/2009 05:37, Uncontrolled Copy, (c) BSI 62561-4 Ed. 1.0 IEC - 2 - 81/313/CD INTRODUCTION This part of IEC 62561-4 deals with the requirements and tests for lightning protection system components (LPSC) used for the installation of a lightning protection (LPS) designed

22、 and implemented according to IEC 62305 series of standards. IEC 62561 consists the following parts, under the general title Lightning protection system components (LPSC): IEC 62561-1 Requirements for connection components IEC 62561-2 Requirements for conductors and earth electrodes IEC 62561-3 Requ

23、irements for isolating spark gaps IEC 62561-4 Requirements for conductor fasteners IEC 62561-7 Requirements for earthing enhancing compounds _ Licensed Copy: London South Bank University, South Bank University, 02/02/2009 05:37, Uncontrolled Copy, (c) BSI 62561-4 Ed. 1.0 IEC - 3 - 81/313/CD Contents

24、 1 Scope 4 2 Normative references 4 3 Definitions 4 3.1 Conductor fastener 4 4 Classification. 4 4.1 According to the material composition 4 4.2 According to fixing arrangement of the conductor within the fastener 4 4.3 According to conductor clamping arrangement. 5 5 Requirements. 5 5.1 General 5 5

25、.2 Environmental requirements . 5 5.3 Mechanical strength 5 5.4 Installation instructions 5 5.5 Marking 5 6 Tests . 6 6.1 General test conditions 6 6.2 Test preparation 6 6.3 Environmental influence test. 7 6.4 Resistant to mechanical effects. 7 6.5 Installation instructions 9 6.6 Marking test. 10 6

26、.7 Construction 10 7 Electromagnetic compatibility (EMC) 10 8 Structure and content of the test report . 10 8.1 Report Identification. 10 8.2 Specimen description 11 8.4 Conductor 11 8.5 Standards and References 11 8.6 Test Procedure 11 8.7 Testing Equipment, description. 11 8.8 Measuring Instrument

27、s description . 11 8.9 Results and parameters recorded. 11 Annex A (normative) Environmental test for metallic fasteners 14 Annex B (normative) Environmental test for non-metallic conductor fasteners Resistance to Ultraviolet light 15 Annex C (normative) Flow chart of Tests. 16 Bibliography. 17 Figu

28、re 1 Basic arrangement of specimens. 11 Figure 2 Basic arrangement of lateral load test 12 Figure 3 Typical arrangement for axial movement test 12 Figure 4 Impact test apparatus. 13 Licensed Copy: London South Bank University, South Bank University, 02/02/2009 05:37, Uncontrolled Copy, (c) BSI 62561

29、-4 Ed. 1.0 IEC - 4 - 81/313/CD 1 Scope This International Standard specifies requirements and tests for: Metallic and non-metallic conductor fasteners that are used in conjunction with the air termination system and down conductors. Fixing of fasteners to the fabric / membrane / gravel roofing of st

30、ructures is not covered by this standard due to the vast number and types used in modern day construction. LPC may also be suitable for use in hazardous atmospheres. Regard should then be taken of the extra requirements necessary for the components to be installed in such conditions. 2 Normative ref

31、erences The following referenced documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. IEC 60068-2-52:1996, Environmental testin

32、g - Part 2: Tests - Test Kb: Salt mist, cyclic (sodium chloride solution) (IEC 60068-2-52:1996) IEC 62305-3:2006, Protection against lightning Part 3: Physical damage to structures and life hazard ISO 4892-2:2006, Plastics Methods of exposure to laboratory light sources Part 2: Xenon arc lamps (ISO

33、4892-2:2006) ISO 6988:1994, Metallic and other non-organic coatings Sulfur dioxide test with general condensation of moisture (ISO 6988:1985) ISO 4892-4:2004, Plastics Methods of Exposure to laboratory light sources Part 4: Open flame carbon arc lamps ISO 6957:1988, Copper alloys Ammonia test for st

34、ress corrosion resistance 3 Definitions For the purpose of this International Standard, the following definitions apply. 3.1 conductor fastener a metallic, non-metallic or composite component designed to retain and support the air termination and down conductor, installed at intervals along the leng

35、th of the conductors. NOTE The conductor fastener may be provided with a means of attachment to a mounting surface 4 Classification Conductor fasteners are classified: 4.1 According to the material composition 4.1.1 Metallic (e.g. hot dip galvanized steel, copper, aluminium, stainless steel) 4.1.2 N

36、on-metallic (e.g. PVC, plastics) 4.1.3 Composite (Combination of metal and plastic) 4.2 According to fixing arrangement of the conductor within the fastener 4.2.1 With screws 4.2.2 Without screws (e.g. clips, springs) Licensed Copy: London South Bank University, South Bank University, 02/02/2009 05:

37、37, Uncontrolled Copy, (c) BSI 62561-4 Ed. 1.0 IEC - 5 - 81/313/CD 4.3 According to conductor clamping arrangement 4.3.1 Fasteners that are designed to clamp the conductor 4.3.2 Fasteners that are designed to allow axial movement of the conductor 5 Requirements 5.1 General The conductor fastener sha

38、ll carry out its function of clamping the conductor in an acceptable and safe manner when subjected to mechanical influences, lightning discharge stress and environmental influences. Conductor fasteners shall be so designed and constructed that safe handling is ensured and that retention and support

39、 for the conductor is provided and that in normal use their performance is reliable and without danger to persons and the surrounding. The material of the conductor fastener shall be compatible with the conductor it is fastening, and the surface material it is fastening on and comply with the tests

40、given in Clause 6. 5.2 Environmental requirements 5.2.1 Corrosion resistance Metallic or composite fasteners shall withstand corrosion effects. Compliance is checked following the manufacturers declaration for the classification of the fastener in accordance with Clause 4 and by test according to 6.

41、3.1 and 6.3.3. 5.2.2 UV resistance Non-metallic and composite fasteners shall withstand UV effects. Compliance is checked following the manufacturers declaration for the classification of the fastener in accordance with Clause 4 and by test according to 6.3.2 and 6.3.3. 5.3 Mechanical strength 5.3.1

42、 Perpendicular and axial loads The design of the conductor fastener shall be such that it carries the perpendicular loads caused by the weight of the conductor, snow, ice and wind and axial loads caused by the thermal expansion contraction of the conductor and its weight. Compliance is checked follo

43、wing the manufacturers declaration for the classification of the fastener in accordance with Clause 4 and by test according to 6.4.1 and 6.4.2. 5.3.2 Impact tests Conductor fasteners shall be so designed and constructed to withstand impact stresses caused accidentally. Compliance is checked by test

44、according to 6.4.3. 5.4 Installation instructions The manufacturer or supplier of the conductor fastener shall provide adequate information in his literature to ensure that the installer can select and install the component in a suitable and safe manner, in accordance with IEC 62305-3. Compliance is

45、 checked by inspection in accordance with 6.5. 5.5 Marking Each conductor fastener shall be marked with: the manufacturers or responsible vendors name or logo or trademark; product identification or type; Licensed Copy: London South Bank University, South Bank University, 02/02/2009 05:37, Uncontrol

46、led Copy, (c) BSI 62561-4 Ed. 1.0 IEC - 6 - 81/313/CD Where it is not possible to make these marks directly onto the product, they shall be on the smallest supplied packaging. NOTE Marking may be applied for example by moulding, pressing, engraving, printing adhesive labels or water slide transfers.

47、 Compliance is checked in accordance with 6.6. 6 Tests 6.1 General test conditions Tests according to this standard are type tests. These tests are of such a nature that, after they have been performed, they need not be repeated unless changes are made to the materials, design or type of manufacturi

48、ng process, which might change the performance characteristics. The standard cannot cover all possible types of fasteners and the way of fixing them on various surfaces of different materials. When required, for these applications, agreement should be obtained between the test engineer and manufactu

49、rer on the specific testing regime. Unless otherwise specified, tests are carried out with the specimens assembled and installed as in normal use according to the manufacturers or suppliers instructions, with the recommended conductor materials, sizes and the tightening torques. The tests shall be carried out in the sequence given after environmental tests of