1、BRITISH STANDARD BS EN 60255-22-1:2008 Measuring relays and protection equipment Part 22-1: Electrical disturbance tests 1 MHz burst immunity tests ICS 29.120.70 ? Copyright British Standards Institution Provided by IHS under license with BSI - Uncontrolled Copy Licensee=Boeing Co/5910770001 Not for

2、 Resale, 08/14/2008 21:08:59 MDTNo reproduction or networking permitted without license from IHS -,-,- BS EN 60255-22-1:2008 This British Standard was published under the authority of the Standards Policy and Strategy Committee on 31 March 2008 BSI 2008 ISBN 978 0 580 58079 6 National foreword This

3、British Standard is the UK implementation of EN 60255-22-1:2008. It is identical to IEC 60255-22-1:2007. It supersedes BS EN 60255-22-1:2005 which is withdrawn. The UK participation in its preparation was entrusted to Technical Committee PEL/95, Measuring relays and protection systems. A list of org

4、anizations represented on this committee can be obtained on request to its secretary. This publication does not purport to include all the necessary provisions of a contract. Users are responsible for its correct application. Compliance with a British Standard cannot confer immunity from legal oblig

5、ations. Amendments/corrigenda issued since publication DateComments Copyright British Standards Institution Provided by IHS under license with BSI - Uncontrolled Copy Licensee=Boeing Co/5910770001 Not for Resale, 08/14/2008 21:08:59 MDTNo reproduction or networking permitted without license from IHS

6、 -,-,- EUROPEAN STANDARD EN 60255-22-1 NORME EUROPENNE EUROPISCHE NORM February 2008 CENELEC European Committee for Electrotechnical Standardization Comit Europen de Normalisation Electrotechnique Europisches Komitee fr Elektrotechnische Normung Central Secretariat: rue de Stassart 35, B - 1050 Brus

7、sels 2008 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members. Ref. No. EN 60255-22-1:2008 E ICS 29.120.70 Supersedes EN 60255-22-1:2005 English version Measuring relays and protection equipment - Part 22-1: Electrical disturbance tests - 1 MHz bu

8、rst immunity tests (IEC 60255-22-1:2007) Relais de mesure et dispositifs de protection - Partie 22-1: Essais dinfluence lectrique - Essais dimmunit londe oscillatoire amortie 1 MHz (CEI 60255-22-1:2007) Messrelais und Schutzeinrichtungen - Teil 22-1: Prfungen der elektrischen Strfestigkeit - Prfung

9、der Strfestigkeit gegen 1-MHz-Strgren (IEC 60255-22-1:2007) This European Standard was approved by CENELEC on 2008-02-01. CENELEC members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard w

10、ithout any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the Central Secretariat or to any CENELEC member. This European Standard exists in three official versions (English, French, German). A version in any other lan

11、guage made by translation under the responsibility of a CENELEC member into its own language and notified to the Central Secretariat has the same status as the official versions. CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Cyprus, the Czech Republic, D

12、enmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and the United Kingdom. Copyright British Standards Institution Provided by IH

13、S under license with BSI - Uncontrolled Copy Licensee=Boeing Co/5910770001 Not for Resale, 08/14/2008 21:08:59 MDTNo reproduction or networking permitted without license from IHS -,-,- Foreword The text of document 95/204/CDV, future edition 3 of IEC 60255-22-1, prepared by IEC TC 95, Measuring rela

14、ys and protection equipment, was submitted to the IEC-CENELEC Parallel Unique Acceptance Procedure and was approved by CENELEC as EN 60255-22-1 on 2008-02-01. This European Standard supersedes EN 60255-22-1:2005. The main differences with respect to EN 60255-22-1:2005 are: this document is based on

15、EN 61000-4-18; a capacitor was added for testing shielded communication lines when earthed at one end only; the test procedure for communication ports is clarified; the length of the communication cable for testing is fixed at 10 m; connection to earth removed in Figure 4 for test generator terminal

16、. The following dates were fixed: latest date by which the EN has to be implemented at national level by publication of an identical national standard or by endorsement (dop) 2008-11-01 latest date by which the national standards conflicting with the EN have to be withdrawn (dow) 2011-02-01 Annex ZA

17、 has been added by CENELEC. _ Endorsement notice The text of the International Standard IEC 60255-22-1:2007 was approved by CENELEC as a European Standard without any modification. _ BS EN 60255-22-1:2008 2 Copyright British Standards Institution Provided by IHS under license with BSI - Uncontrolled

18、 Copy Licensee=Boeing Co/5910770001 Not for Resale, 08/14/2008 21:08:59 MDTNo reproduction or networking permitted without license from IHS -,-,- CONTENTS 1 Scope and object4 2 Normative references4 3 Terms and definitions .4 4 Test severity levels .6 5 Test equipment.6 6 Test set-up .9 7 Test proce

19、dure .10 8 Criteria for acceptance11 9 Test report12 Figure 1 Ports for measuring relays and protection equipment 6 Figure 2 Common mode test between each independent port and earth7 Figure 3 Common mode test between each independent port and all other independent ports coupled to earth8 Figure 4 Di

20、fferential mode test9 Figure 5 Test set-up for communication ports with shielded and unshielded cables .11 Table 1 Test voltages for the EUT ports6 Table 2 Criteria for acceptance.11 BS EN 60255-22-1:2008 3 Annex ZA (normative) Normative references to international publications with their correspond

21、ing European publications13 Copyright British Standards Institution Provided by IHS under license with BSI - Uncontrolled Copy Licensee=Boeing Co/5910770001 Not for Resale, 08/14/2008 21:08:59 MDTNo reproduction or networking permitted without license from IHS -,-,- MEASURING RELAYS AND PROTECTION E

22、QUIPMENT Part 22-1: Electrical disturbance tests 1 MHz burst immunity tests 1 Scope and object This part of IEC 60255 is based on IEC 61000-4-18, referring to that publication where applicable, and specifies the general requirements for 1 MHz oscillatory wave immunity tests for measuring relays and

23、protection equipment for power system protection, including the control, monitoring and process interface equipment used with the relays and protection equipment. The objective of the tests is to confirm that the equipment under test will operate correctly when energised and subjected to repetitive

24、damped oscillatory waves such as those originating from closing or opening circuit breakers or disconnectors in high voltage substations or power plants. The requirements specified in this standard are applicable to measuring relays and protection equipment in a new condition and all tests specified

25、 are type tests only. The object of this standard is to state: definition of terms used; test severity levels; test equipment; test set-up; test procedure; criteria for acceptance; test report. 2 Normative references The following referenced documents are indispensable for the application of this do

26、cument. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. IEC 60255-6, Electrical relays Part 6: Measuring relays and protection equipment IEC 61000-4-18:2006, Electromagnetic Compatibility

27、(EMC) Part 4-18: Testing and measurement techniques Damped oscillatory wave immunity test 3 Terms and definitions For the purposes of this document, the following terms and definitions apply. BS EN 60255-22-1:2008 4 Copyright British Standards Institution Provided by IHS under license with BSI - Unc

28、ontrolled Copy Licensee=Boeing Co/5910770001 Not for Resale, 08/14/2008 21:08:59 MDTNo reproduction or networking permitted without license from IHS -,-,- 3.1 auxiliary equipment equipment necessary to provide the EUT with the signals required for normal operation and equipment to verify the perform

29、ance of the EUT 3.2 auxiliary power supply port AC or DC auxiliary energising input of the EUT 3.3 burst a sequence of a limited number of distinct pulses or an oscillation of limited duration. IEV 161-02-07 3.4 communication port interface with a communication and/or control system, using low energ

30、y signals, permanently connected to the EUT 3.5 EUT Equipment Under Test, which may be either a measuring relay or a protection equipment 3.6 functional earth port a port on the EUT which is connected to earth for purposes other than electrical safety 3.7 input port port through which the EUT is ene

31、rgised or controlled in order to perform its function(s), e.g. current and voltage transformer, status (binary) inputs, etc. IEV 131-12-61, modified 3.8 output port port through which the EUT produces predetermined changes, e.g. contact, optocoupler, analogue outputs, etc. IEV 131-12-62, modified 3.

32、9 port particular interface of the EUT with the external electromagnetic environment (see Figure 1) IEC 61000-4-18, 3.10 BS EN 60255-22-1:2008 5 Copyright British Standards Institution Provided by IHS under license with BSI - Uncontrolled Copy Licensee=Boeing Co/5910770001 Not for Resale, 08/14/2008

33、 21:08:59 MDTNo reproduction or networking permitted without license from IHS -,-,- Auxiliary power supply port Functional earth port Output port Input port Communication port EUT Figure 1 Ports for measuring relays and protection equipment 4 Test severity levels The test voltages for the appropriat

34、e ports of the EUT are shown in Table 1. Table 1 Test voltages for the EUT ports Test voltage (kV peak 10 %) Oscillation frequency 1 MHz Port under test Common mode test Differential mode test Auxiliary power supply 2,5 1 Input and output (see note) 2,5 1 Communication 1 0 NOTE In more severe enviro

35、nments a differential test voltage of 2,5 kV may be required for current and voltage transformer inputs. The 1 MHz test is not applicable to functional earth port. The 1 MHz test is not applicable to the communications port if interfacing with cables which are not permanently connected, or whose tot

36、al length according to the manufacturers functional specification is always less than 3 m. 5 Test equipment The test generator, characteristics and performance are specified in IEC 61000-4-18. The coupling and decoupling networks shall be in accordance with the arrangements in Figures 2, 3 and 4 of

37、this part of IEC 60255. IEC 1978/07 BS EN 60255-22-1:2008 6 Copyright British Standards Institution Provided by IHS under license with BSI - Uncontrolled Copy Licensee=Boeing Co/5910770001 Not for Resale, 08/14/2008 21:08:59 MDTNo reproduction or networking permitted without license from IHS -,-,- G

38、round reference plane EUT Insulating support Auxiliary equipment L 1 2 3 4 Coupling/ decoupling network L L L L L L L Test generator CC IEC 1979/07 Key L high-frequency blocking inductor, 1,5 mH C high-frequency coupling capacitor, 0,5 F 1, 2, 3, 4 EUT input and output ports Figure 2 Common mode tes

39、t between each independent port and earth BS EN 60255-22-1:2008 7 Copyright British Standards Institution Provided by IHS under license with BSI - Uncontrolled Copy Licensee=Boeing Co/5910770001 Not for Resale, 08/14/2008 21:08:59 MDTNo reproduction or networking permitted without license from IHS -

40、,-,- EUT L C 1 2 3 4 L L L L L L L CCC CCCC Ground reference plane Insulating support Auxiliary equipment Coupling/ decoupling network Test generator IEC 1980/07 Key L high-frequency blocking inductor, 1,5 mH C high-frequency coupling capacitor, 0,5 F 1, 2, 3, 4 EUT input and output ports Figure 3 C

41、ommon mode test between each independent port and all other independent ports coupled to earth BS EN 60255-22-1:2008 8 Copyright British Standards Institution Provided by IHS under license with BSI - Uncontrolled Copy Licensee=Boeing Co/5910770001 Not for Resale, 08/14/2008 21:08:59 MDTNo reproducti

42、on or networking permitted without license from IHS -,-,- EUT L 1 2 3 4 L L L L L L L CC Ground reference plane Insulating support Auxiliary equipment Coupling/ decoupling network Test generator IEC 1981/07 Key L high-frequency blocking inductor, 1,5 mH C high-frequency coupling capacitor, 0,5 F 1,

43、2, 3, 4 EUT input and output ports Figure 4 Differential mode test 6 Test set-up The general test set-up is specified in IEC 61000-4-18. All auxiliary equipment used to provide the EUT with signals for normal operation, and to verify the correct operation of the EUT, shall be decoupled, so that the

44、test voltage does not affect the auxiliary equipment. The length of leads between the test generator and the coupling/decoupling network shall be as short as possible. The test leads used between the EUT and the coupling/decoupling network shall not be longer than 2 m. The EUT and test leads shall b

45、e placed on an insulating support 0,1 m above the ground reference plane. The minimum distance between the EUT and all other conductive structures BS EN 60255-22-1:2008 9 Copyright British Standards Institution Provided by IHS under license with BSI - Uncontrolled Copy Licensee=Boeing Co/5910770001

46、Not for Resale, 08/14/2008 21:08:59 MDTNo reproduction or networking permitted without license from IHS -,-,- (for example the walls of a shielded room) except the ground reference plane beneath the EUT, shall be 0,5 m. The EUT shall be tested in its case with the cover in position. Where the EUT is

47、 exclusively mounted in a cubicle, the tests may be conducted with the EUT in the cubicle. The cubicle, test leads and interconnecting cables shall be placed on an insulating support, 0,1 m above the ground reference plane. All parts of the EUT intended to be earthed, shall be earthed. The test set-up for common and differential mode tests are shown in Figures 2, 3 and 4. For communication ports, the length of shielded or unshielded cable between EUT