IEEE-C37.013A-2007.pdf

上传人:椰子壳 文档编号:3770074 上传时间:2019-09-23 格式:PDF 页数:26 大小:544.52KB
返回 下载 相关 举报
IEEE-C37.013A-2007.pdf_第1页
第1页 / 共26页
IEEE-C37.013A-2007.pdf_第2页
第2页 / 共26页
IEEE-C37.013A-2007.pdf_第3页
第3页 / 共26页
IEEE-C37.013A-2007.pdf_第4页
第4页 / 共26页
IEEE-C37.013A-2007.pdf_第5页
第5页 / 共26页
亲,该文档总共26页,到这儿已超出免费预览范围,如果喜欢就下载吧!
资源描述

《IEEE-C37.013A-2007.pdf》由会员分享,可在线阅读,更多相关《IEEE-C37.013A-2007.pdf(26页珍藏版)》请在三一文库上搜索。

1、IEEE Std C37.013a-2007 (Amendment to IEEE Std C37.013-1997) IEEE Standard for AC High Voltage Generator Circuit Breakers Rated on a Symmetrical Current Basis Amendment 1: Supplement for Use with Generators Rated 10100 MVA I E E E 3 Park Avenue New York, NY 10016-5997, USA 6 June 2007 IEEE Power Engi

2、neering Society Sponsored by the Switchgear Committee -,-,- IEEE Std C37.013a-2007 IEEE Standard for AC High Voltage Generator Circuit Breakers Rated on a Symmetrical Current Basis Amendment 1: Supplement for Use with Generators Rated 10100 MVA Sponsor Switchgear Committee of the IEEE Power Engineer

3、ing Society Approved 8 March 2007 IEEE-SA Standards Board -,-,- The Working Group thanks the International Electrotechnical Commission (IEC) for permission to reproduce information from its International Standard IEC 60694 (2002) and IEC 602271-100 (2006). All such extracts are copyright of IEC, Gen

4、eva, Switzerland. All rights reserved. Further information on the IEC is available from www.iec.ch. IEC has no responsibility for the placement and context in which the extracts and contents are reproduced by the author, nor is IEC in any way responsible for the other content or accuracy therein. Ab

5、stract: This amendment includes special requirements better suited for generator circuit breakers used to protect smaller generators rated between 10 MVA and 50 MVA and between 50 MVA and 100 MVA. It is important because the existing standards for typical distribution circuit breakers specifically e

6、xclude generator circuit breakers from the scope. Keywords: circuit breaker, generator, generator circuit breaker, high voltage, transformer _ The Institute of Electrical and Electronics Engineers, Inc. 3 Park Avenue, New York, NY 10016-5997, USA Copyright 2007 by the Institute of Electrical and Ele

7、ctronics Engineers, Inc. All rights reserved. Published 6 June 2007. Printed in the United States of America. IEEE is a registered trademark in the U.S. Patent +1 978 750 8400. Permission to photocopy portions of any individual standard for educational classroom use can also be obtained through the

8、Copyright Clearance Center. iv Copyright 2007 IEEE. All rights reserved. Introduction The 1997 edition of IEEE Std C37.013, although approved as an IEEE Standard, failed to win approval as an ANSI standard because, although the Scope says that it covers “all ac high-voltage generator circuit breaker

9、s,” the requirements for small generator circuit breakers were not adequately addressed. It is the main purpose of this supplement to add specific requirements for smaller generator circuit applications, and focusing in particular on circuit breakers for use with generators rated in the 10 MVA to 10

10、0 MVA range. The supplement includes additional preferred ratings as well as other requirements that supplement the main requirements of 1997 edition. One important addition can be found in Annex B, which gives guidance regarding the effects of cable connections on the transient recovery voltage req

11、uirements for generator circuits. It would be well to mention two items, which were proposed for change, but in the end were not incorporated: a) It was proposed that in 5.5 of IEEE Std C37.013-1997, an alternative rated short-circuit duty cycle, CO 30 s CO, should be added to the existing preferred

12、 duty cycle of CO 30 min CO. After much discussion, it was decided that, even if circuit breakers were available with the faster 30 s reclosing time, most likely it would never be needed. If there were a fault on either the transformer-side or the generator-side of the circuit breaker, it would be h

13、ighly unlikely that such a fault could clear itself, so that an attempted reclosing operation would probably be unsuccessful anyway. Furthermore, it would take at least 30 minutes for someone to go to check the circuit to verify whether it should be reclosed. Therefore, the “CO 30 min CO” remains th

14、e preferred duty cycle. b) It was proposed that, in Figure 15 of IEEE Std C37.013-1997, the parameters u and t should be defined for the coordinates of the upper end point on the “delay line” and that preferred values should be established for those parameters. After much discussion, it was conclude

15、d that, as the transient recovery voltage wave will have begun to bend away from the upper end of the delay line, the actual end point is not critical, and therefore, it is not specified. Notice to users Errata Errata, if any, for this and all other standards can be accessed at the following URL: ht

16、tp:/ standards.ieee.org/reading/ieee/updates/errata/index.html. Users are encouraged to check this URL for errata periodically. Interpretations Current interpretations can be accessed at the following URL: http:/standards.ieee.org/reading/ieee/interp/ index.html. This introduction is not part of IEE

17、E Std C37.013a-2007, IEEE Standard for AC High Voltage Generator Circuit Breakers Rated on a Symmetrical Current BasisAmendment 1: Supplement for use with Generators Rated 10100 MVA. v Copyright 2007 IEEE. All rights reserved. Patents Attention is called to the possibility that implementation of thi

18、s amendment may require use of subject matter covered by patent rights. By publication of this amendment, no position is taken with respect to the existence or validity of any patent rights in connection therewith. The IEEE shall not be responsible for identifying patents or patent applications for

19、which a license may be required to implement an IEEE standard or for conducting inquiries into the legal validity or scope of those patents that are brought to its attention. Participants At the time this amendment was completed, the Small Generator Circuit Breaker Supplement Working Group had the f

20、ollowing membership: R. William Long, Chair Anne Bosma Dieter Braun Denis Dufournet Georges Montillet Neal McCord Nigel P. McQuin Martin Motz Erich Ruoss H. Melvin Smith Gerald J. Watson The following members of the individual balloting committee voted on this amendment. Balloters may have voted for

21、 approval, disapproval, or abstention. Roy Alexander W. J. (Bill) Bergman Stan Billings Anne Bosma Dieter Braun Lyne Brisson Ted Burse Tommy Cooper Ronald Daubert Dufournet Denis Alexander Dixon Doug Edwards Gary Engmann Marcel Fortin William G. Fossey Ruben Garzon Douglas Giraud Keith Gray Randall

22、Groves Erik Guillot Harold L. Hess Edward Horgan Jr. David Jackson Richard Jackson Jerry Jerabek Stephen R. Lambert John Leach Jason Lin Albert Livshitz Franco Lo Monaco R. William Long Gregory Luri William Majeski Neil McCord Nigel P. McQuin Gary Michel Daleep Mohla Georges Montillet Arun Narang Je

23、ffrey Nelson Paul Notarian T. W. Olsen Miklos Orosz David Peelo Ralph Philbrook III James Ruggieri Devki Sharma Jordan Shikoski H. Melvin Smith R. Kirkland Smith Allan St. Peter Stanton Telander Shanmugan Thamilarasan Gerald Vaughn Charles Wagner James Wilson Zhenxue Xu -,-,- vi Copyright 2007 IEEE.

24、 All rights reserved. When the IEEE-SA Standards Board approved this amendment on 8 March 2007, it had the following membership: Steve M. Mills, Chair Richard H. Hulett, Vice Chair Don Wright, Past Chair Judith Gorman, Secretary Richard DeBlasio Alex Gelman William R. Goldbach Arnold M. Greenspan Ro

25、bert M. Grow Joanna N. Guenin Julian Forster* Kenneth S. Hanus William B. Hopf Herman Koch Joseph L. Koepfinger* John Kulick David J. Law Glenn Parsons Ronald C. Petersen Tom A. Prevost Narayanan Ramachandran Greg Ratta Robby Robson Anne-Marie Sahazizian Virginia C. Sulzberger Malcolm V. Thaden Rich

26、ard L. Townsend Walter Weigel Howard L. Wolfman *Member Emeritus Also included are the following nonvoting IEEE-SA Standards Board liaisons: Satish K. Aggarwal, NRC Representative Richard DeBlasio, DOE Representative Alan H. Cookson, NIST Representative Don Messina IEEE Standards Program Manager, Do

27、cument Development Matthew J. Ceglia IEEE Standards Program Manager, Technical Program Development -,-,- vi Copyright 2007 IEEE. All rights reserved. Contents 1. Scope 1 2. References 2 5. Ratings and required capabilities 2 5.3 Rated continuous current. 2 5.8 Short-circuit current rating 3 5.10 Rat

28、ed load current switching capability. 7 5.12 Out-of-phase current switching ability 9 6. Tests . 10 7. Application guide. 12 8. Bibliography. 12 Annex B (informative) For generator circuit breakers connected to the step-up transformer by shielded cablesan example of the effects of added capacitance

29、on TRV requirements for a system-source fault. 13 -,-,- 1 Copyright 2007 IEEE. All rights reserved. IEEE Standard for AC High Voltage Generator Circuit Breakers Rated on a Symmetrical Current Basis Amendment 1: Supplement for Use with Generators Rated 10100 MVA NOTEThe editing instructions contained

30、 in this amendment define how to merge the material contained herein into the existing base standard and its amendments to form the comprehensive standard. The editing instructions are shown in bold italic. Four editing instructions are used: change, delete, insert, and replace. Change is used to ma

31、ke corrections in existing text or tables. The editing instruction specifies the location of the change and describes what is being changed by using strikethrough (to remove old material) and underscore (to add new material). Delete removes existing material. Insert adds new material without disturb

32、ing the existing material. Insertions may require renumbering. If so, renumbering instructions are given in the editing instruction. Replace is used to make changes in figures or equations by removing the existing figure or equation and replacing it with a new one. Editorial notes will not be carrie

33、d over into future editions because the changes will be incorporated into the base standard. 1. Scope Change the existing paragraph as shown: This standard applies to all ac high-voltage generator circuit breakers rated on a symmetrical current basis that are installed between the generator and the

34、transformer terminals. Requirements relative to ac high- voltage generator circuit breakers intended for use with generators and transformers rated 10 MVA or more are covered specifically. Generator circuits rated less than 10 MVA and pumped storage installations are considered a special application

35、s, and their requirements are not completely covered by this standard. -,-,- IEEE Std C37.013a-2007 IEEE Standard for AC High Voltage Generator Circuit Breakers Rated on a Symmetrical Current BasisAmendment 1: Supplement for use with Generators Rated 10100 MVA 2 Copyright 2007 IEEE. All rights reser

36、ved. 2. References Change the following references in Clause 2 as shown: ANSI C37.06-1987 2000(R1994), Switchgear: AC High-Voltage Circuit Breakers Rated on a Symmetrical Current BasisPreferred Ratings and Related Required Capabilities.1 IEC 60694: 1996Edition 2.2 (2002-01), Common specifications fo

37、r high voltage switchgear and controlgear standards.2 IEEE Std C37.04TM-19941999, IEEE Standard Rating Structure for AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis (ANSI).3, 4 NEMA SG 4-19902000, Alternating Current High-Voltage Circuit Breaker.5 Insert the following reference

38、s into Clause 2 in alphanumeric order, and keep the existing reference to the prior edition of IEEE Std C37.09TM-1979 that covers two-part testing: IEC 62271-100 Edition 1.1 (2003-05), High-voltage switchgear and controlgearPart 100: High-voltage alternating-current circuit-breakers. IEEE Std C37.09

39、TM-1999, IEEE Standard Test Procedure for AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis. IEEE Std C37.11TM-1997 (Reaff 2003), IEEE Standard Requirements for Electrical Control for AC High- Voltage Circuit Breakers Rated on a Symmetrical Current Basis or a Total Current Basis.

40、 5. Ratings and required capabilities 5.3 Rated continuous current Change the following paragraph as shown: The rated continuous current of a generator circuit breaker is the designated upper limit of current in rms amperes at power frequency, which it shall be required to carry continuously without

41、 exceeding any of the limitations designated in 5.3.1 and 5.3.2. Typical values include 1.2 kA, 1.6 kA, 2 kA, 2.5 kA, 3.15 kA, 4 kA, 5 kA, 6.3 kA, 8 kA, 10 kA, 12 kA, 16 kA, 20 kA, etc and so on. 1 ANSI publications are available from the Sales Department, American National Standards Institute, 25 W

42、est 43rd Street, 4th Floor, New York, NY 10036, USA (http:/www.ansi.org/). 2 IEC publications are available from the Sales Department of the International Electrotechnical Commission, Case Postale 131, 3, rue de Varemb, CH-1211, Genve 20, Switzerland/Suisse (http:/www.iec.ch/). IEC publications are

43、also available in the United States from the Sales Department, American National Standards Institute, 25 West 43rd Street, 4th Floor, New York, NY 10036, USA (http:/www.ansi.org/). 3 IEEE publications are available from the Institute of Electrical and Electronics Engineers, Inc., 445 Hoes Lane, Pisc

44、ataway, NJ 08854, USA (http:/standards.ieee.org/). 4 The IEEE standards or products referred to in this clause are trademarks of the Institute of Electrical and Electronics Engineers, Inc. 5 NEMA publications are available from Global Engineering Documents, 15 Inverness Way East, Englewood, CO 80112

45、, USA (http:/ -,-,- IEEE Std C37.013a-2007 IEEE Standard for AC High Voltage Generator Circuit Breakers Rated on a Symmetrical Current BasisAmendment 1: Supplement for use with Generators Rated 10100 MVA 3 Copyright 2007 IEEE. All rights reserved. 5.4.1 Dielectric strength of external insulation Rep

46、lace Table 4 with the following: Table 4Schedule of dielectric strength values for ac generator circuit breakers and external insulation (Ref. IEC)a (Ref. ANSI) Insulation withstand voltagesb Rated voltage (kV, rms) Rated maximum voltage (kV, rms) Power frequency (kV, rms) Lightning impulse 1.2 50 s

47、 wave (kV, peak) Line Column 1 Column 2 Column 3 Column 4 1 7.2 5 20 60 2 12 8.25 28 75 3 17.5 8.25 / 15 38 95 4 15.5 50 110 5 24 27 60 125 6 36 38 80 150c a Reprinted from 4.1.1 and Table 1a of IEC 60694 Ed. 2.2 “Copyright 2002 IEC, Geneva, Switzerland. www.iec.ch.” b For rated voltages between tho

48、se listed in Column 1 or in Column 2, the higher values of insulation withstand voltage should be chosen from the higher line number in the table. c In Line 6 of Table 4, the Lightning Impulse Withstand Voltage value is not 170 kV, as no generators are rated 36 kV with a rated Lightning Impulse Withstand Voltage of 170 kV. 5.8 Short-circuit current rating Insert the following text at the end of the existing paragraph: The short-circuit current rating of a generator circuit breaker i

展开阅读全文
相关资源
猜你喜欢
相关搜索

当前位置:首页 > 其他


经营许可证编号:宁ICP备18001539号-1