《ANSI-SPRI-IA-1-2005.pdf》由会员分享,可在线阅读,更多相关《ANSI-SPRI-IA-1-2005.pdf(9页珍藏版)》请在三一文库上搜索。
1、Approved May 16, 2005 ANSI/SPRI IA-1 2005 DISCLAIMER SPRI and its members and agents do not warrant the testing procedure contained herein as proper under all conditions. SPRI EXPRESSLY DISCLAIMS ANY RESPONSIBILITY FOR DAMAGES ARISING FROM THE USE, APPLICATION. OR RELIANCE ON THE TESTING PROCEDURE C
2、ONTAINED HEREIN. Copyright 2005 by SPRI. All Rights Reserved Standard Field Test Procedure for Determining the Mechanical Uplift Resistance of Insulation Adhesives over Various Substrates I. Purpose of the Test This standard specifies a field-testing procedure to determine the mechanical uplift resi
3、stance of a specific roof insulation/adhesive combination. II. Scope This testing procedure encompasses various types of insulation adhesives, substrates and insulations. III. Equipment (See Commentary 1 b. Cohesive: Fracture of adhesive structure; c. Insulation delamination: Facer separation from i
4、nsulation core; or d. Insulation Fracture: Structural break-up of insulation. O. The actual instrument readings reflect the tare weight + the pounds (kN) of force resisted by the tested assembly. Actual pressure calculations shall be made by subtracting the tare weight from the instrument reading an
5、d dividing that number by the total area of the sample size tested. P. Precision and Bias Based on tests performed at a SPRI member company laboratory, the test procedure has a sample-to-sample precision of 10% at the 95% confidence level*. No information can be given on the bias of this test proced
6、ure for measuring the mechanical uplift resistance of insulation adhesives because no test material having an accepted reference value is available. * Test results available through SPRI headquarters. Approved May 16, 2005 ANSI/SPRI IA-1 2005 (3) Copyright 2005 by SPRI. All Rights Reserved Commentar
7、y to Standard Field Test Procedure for Determining the Mechanical Uplift Resistance of Insulation Adhesives over Various Substrates This Commentary consists of explanatory and supplementary material designed to help the user understand the requirements of the Standard through brief explanations of t
8、he reasoning employed in arriving at these requirements and is not considered a part of the ANSI standard. This standard is intended primarily for situations when an existing roofing system is being replaced or recovered and the general condition of the substrate is in doubt. This procedure, however
9、, is also applicable to new construction. CIII. Equipment (See Table A) Examples of appropriate pull testers are: COMTEN HYDRAJAWS CIV.A Test Area Tests should also be performed in areas where the roof may have been damaged or where water or other chemicals have infiltrated the roof system. These el
10、ements may have caused the roof deck or other components to deteriorate and cause lower pull values. (See Figure A) CIV.B Sample Size CB. Other sized plates may be used, however the data from tests using other than the 2 x 2 plate may not be consistent with data from the standard test specimen. Spec
11、imen size shall not be smaller than 2 times the on center spacing of the adhesive beads. (See Figure B) CIV.E Temperature of test The insulation adhesive manufacturer should be consulted concerning the application temperature limitations of the adhesive. Certain deck types (gypsum, cementitious wood
12、 fiber, or lightweight insulating concrete) may be affected by free water. Pull values obtained over decks in a frozen state may be elevated and therefore unreliable. CIV.K.c Determination of failure Failure could occur at the substrate/first layer intersection or any other subsequent adhered inters
13、ections. It could also occur within the insulation itself, such as the facer lifting off or the core separating, or failure of the substrate. Separation of the test specimen from the plywood shall not be considered a failure of the adhesive. The value should still be recorded as it may exceed the de
14、sign value for the specific project. CIV.K.e The lowest test value should be used as the design load resistance value, unless it is shown to be an anomaly. On certain projects, it may be necessary to perform additional pull tests beyond the minimum number required. This includes, but is not limited
15、to, occasions when: pull values vary significantly tests are performed in decks that are inherently less consistent such as lightweight insulating concrete, cementitious wood fiber, and gypsum there exist multiple damaged or questionable areas local building codes require additional tests roofs are
16、subject to high wind loading If there are anomalies in pull values, the deck should be inspected by a qualified professional to determine the cause. CIV.O The actual instrument readings reflect the tare weight + the pounds (kN) of force resisted by the tested assembly. Tare weight is the weight of t
17、he plate or plywood and the means used to connect the test sample to the load cell. Actual pressure calculations are made by subtracting the tare weight from the instrument reading and dividing that number by the total area of the sample size tested. For example: On a 24” x 24” (0.6096m x 0.6096m) (
18、4 sq. ft.) sample, if the tare weight is 10 lbs. (0.0445kN) and the instrument reading is 1010 lbs. (4.4927kN), the calculated uplift resistance of the assembly is (1010 lbs 10 lbs) / 4 ft2 = 250 psf (4.4927kN 0.0445kN) / 0.3716 sq. m. = 11.97 KPA) Approved May 16, 2005 ANSI/SPRI IA-1 2005 (4) Copyr
19、ight 2005 by SPRI. All Rights Reserved Personnel A person who has been trained in the pull test procedure should perform the tests. A representative of the building owner should be present to witness the tests and verify the values. A roofing professional should also be present to repair the test ar
20、eas and return the roof area to a watertight condition. Cautions See Commentary CIV.E Deck Loading This test does not indicate the suitability of the existing roof (if being recovered), the deck or the decks ability to withstand the uplift loads calculated by this procedure. A structural engineer or
21、 roofing design professional should obtain this information. Table A Equipment Contact Information Com-Ten Industries, Inc. Address: 6405 49th Street North Pinellas Park, FL 33781 Telephone: (727) 520-1200 Fax: (727) 520-0299 E-mail: Salescom- Website: - Hydrajaws Ltd. 3 Tile Cross Trading Estate Ti
22、le Cross Birmingham, B33 0NW, England Telephone: +44 (0)121 779 6856/7 Fax: +44 (0)121 779 6880 E-mail: testerhydrajaws.co.uk Figure A Cross Section of Assembly Approved May 16, 2005 ANSI/SPRI IA-1 2005 (5) Copyright 2005 by SPRI. All Rights Reserved Figure B BEAD PLACEMENT EXAMPLES 12”oc 6”oc 12” 6
23、” 6” 6” 6” C 6” 3” C3” 24” (.6096m) x 24”(.6096m) SPECIMEN SIZE Approved May 16, 2005 ANSI/SPRI IA-1 2005 (6) Copyright 2005 by SPRI. All Rights Reserved Appendix A Insulation Test Report The following three pages contain Forms A, B and C. These forms or similar ones shall be used to report Mechanic
24、al Uplift Resistance of Insulation Adhesives test results. Approved May 16, 2005 ANSI/SPRI IA-1 2005 (7) Copyright 2005 by SPRI. All Rights Reserved Insulation Adhesive Test Report Form A Job Name: _ Test Date: _ Location: _ Ambient Temp: _ Roof Area:_ sq. ft.(sq. m) Tester Mfgr/Model: _ Max. Cap. O
25、f Tester: _ Check One: ? lbf ? kN Date of Last Calibration:_ Number of Tests Recorded on Form C: _ Insulation Manufacturer: _ Adhesive Manufacturer: _ Insulation Type: _ Adhesive Type: _ Insulation Thickness: _ Test Performed by: _ Witnessed By: _ Test Cut Areas Repaired By: _ Project Type: ?New Con
26、struction ?Tear-Off ?Retrofit DECK TYPE ? Steel: Gauge: _ ? Structural Concrete Thickness: _ Check One: ? Poured In Place ? Precast ? Lightweight Concrete Thickness: _ ? Insulating Concrete Thickness: _ ? Cementitious Wood Fiber Thickness: _ ? Gypsum Thickness: _ Check One: ? Poured In Place ? Preca
27、st ? Wood Thickness: _ Check One: ? OSB ? Plywood ? Plank ? Fiberglass Thickness: _ ? Other: Thickness: _ Optional Information: Test Time:_ Building Height: _ Thickness of Existing Roof Assembly: _ New Roofing System Manufacturer: _ Roof Cover Type (Check One): ? Mechanically Attached Single-ply ? M
28、odified Bitumen ? Ballasted Single-ply ? Built-up Roofing ? Fully Adhered Single-ply ? Other: _ DISCLAIMER: MANUFACTURERS INSTALLATION REQUIREMENTS SHALL BE FOLLOWED WHEN USING ANY OF THE TESTED ADHESIVES. NEITHER THE TECHNICIAN PERFORMING THE PULLOUT TESTS NOR HIS/HER COMPANY IS RESPONSIBLE FOR THE
29、 WATERPROOFING INTEGRITY OF THE REPAIRS. THIS TEST REPORT DOES NOT CERTIFY THE STRUCTURAL INTEGRITY OF THE ROOF DECK. Approved May 16, 2005 ANSI/SPRI IA-1 2005 (8) Copyright 2005 by SPRI. All Rights Reserved Insulation Adhesive Test Report Form B Job Name: _ Test Date: _ Roof Plan (Not to Scale) Ide
30、ntify where tests were performed, showing corresponding test number from Form C Approved May 16, 2005 ANSI/SPRI IA-1 2005 (9) Copyright 2005 by SPRI. All Rights Reserved Insulation Adhesive Test Report Form C (Refer To the “Standard Field Test Procedure for Determining the Mechanical Uplift Resistan
31、ce of Insulation Adhesives over Various Substrates” for full documentation) Job Name: _ Test Date: _ ? Tare Weight _ A B C D E F Test No. Location On Roof (Roof Plan on form B) Measurement Pounds Force (lbf) (kN) ? Less Tare ? = ? - ? lbf (kN) Resistance ?= ? 4.0 (.3716sq m) pounds/sq.ft psf Sample Size 24”x24” (.6096m x.6096m) Failure Mode 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Comments: _